Active Line Modules With External Air Cooling; Description - Siemens SINAMICS Series Equipment Manual

Booksize power modules
Hide thumbs Also See for SINAMICS Series:
Table of Contents

Advertisement

3.3

Active Line Modules with External Air Cooling

3.3
3.3.1

Description

The Motor Modules are connected to the power supply network via the Active Line Modules
with external air cooling, which provide the Motor Modules with a constant DC link voltage.
This ensures that they are not influenced by network fluctuations.
When the motors are in feedback mode, Active Line Modules supply power back to the
network. The regenerative feedback capability of the modules can be deactivated by
parameterization.
The DC link starts precharging as soon as the supply voltage is applied and is independent
of its phase sequence direction. Load can be applied to the DC link after the modules have
been enabled. An optional main contactor is required for disconnecting the voltage.
The Active Line Modules are suitable for direct operation on TN, IT, and TT systems.
External air cooling uses the "through-hole" method. This is a cooling method for SINAMICS
power units that is only available for booksize devices. The power unit and its heat sink can
be inserted in a rectangular knockout at the rear of the switching cabinet and mounted with a
seal. The heat sink and the fan (included in the scope of supply) project beyond the rear of
the switching cabinet and the heat is dissipated outside the switching cabinet or in a
separate air duct.
Equipment Manuel for Booksize Power Modules
Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2
3.3 Active Line Modules with External Air Cooling
Line Modules Booksize
3-21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics s120

Table of Contents