3.5 Smart Line Modules (16 kW and 36 kW) with internal air cooling
3.5.3.5

EP terminals X21

Table 3-31
Terminal block X21
Terminal
1
2
3
4
Max. connectable cross-section: 1.5 mm
Type: Screw terminal 1 (see Connection Methods)
Warning
For operation, 24 V DC must be connected to terminal 3 and ground to terminal 4. Upon
removal, pulse inhibit is activated. Feedback is deactivated and the bypass relay drops out.
If the Line Module is not disconnected from the network when the EP terminal is deactivated
(e.g. a main contactor is not installed), the DC link remains charged.
Notice
If a drive line-up is switched off by means of the line disconnecting device, the voltage at
terminals 3 (EP +24 V) and 4 (EP M) must be interrupted beforehand. This can be carried
out using a leading breaking auxiliary contact (≥ 10 ms), for example.
3.5.3.6

X24 24 V terminal adapter

Table 3-32
Terminal block X24
Terminal
+
M
The 24 V terminal adapter is supplied as standard
Max. connectable cross-section: 6 mm
Type: Screw terminal 5 (see Connection Methods)
3-66
Name
Reserved, do not use
Reserved, do not use
EP +24 V (Enable Pulses)
EP M (Enable Pulses)
2
Name
24 V power supply
Ground
2
Technical specifications
Voltage 24 V DC
Current consumption: 10 mA
Isolated input
Signal propagation times:
L → H 100 μs
H → L: 1000 μs
Technical specifications
24 V DC supply voltage
Electronic ground
Equipment Manuel for Booksize Power Modules
Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2