Service and Support Booksize
8.2 Replacing Fans
Removing the fan:
1. Disconnect the power supply (24 V DC and 400 V AC)
Wait 5 minutes while the DC link energy discharges!
2. Remove the component from the drive line-up.
3. Open the fan cover.
Module width: 50 mm
4. Remove the fan.
5. Remove the connector.
Replacing a fan in a module with a width of 300 mm: See: Motor Modules with Internal Air
Cooling – Installation
Installing the fan:
1. Before installing the fan, check the through-flow direction
2. Insert the connector fully.
3. Insert the fan fully.
4. Close the fan cover.
8-2
Module width: 100 mm
(the arrow on the fan must point towards the fins).
Do not squash the connection cables!
Module width: 150 mm and 200 mm