2.3.3.2

Line/load connection

The Basic Line Filter for Active Line Modules is rated for a voltage range of 380 V 3AC -10%
to 480 V 3AC +10% (-15% <1 min) at 47 Hz to 63 Hz.
Table 2-2
Type of connection
Terminals
Line connection (line)
Load connection (load)
Basic Line Filter for Active Line Modules
16 kW
36 kW
55 kW
1) for ring cable lugs to DIN 46234
Equipment Manuel for Booksize Power Modules
Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2
Designations
L1, L2, L3, PE
L1´, L2´, L3´, PE
Screw terminal: 10 mm
3-pin/1.5 Nm (see Screw Terminals)
2
PE connection: M6/3 Nm
Screw terminal: 35 mm
2
PE connection: M6/3 Nm
Screw terminal: 50 mm
2
PE connection: M6/3 Nm
2.3 Basic Line Filter for Active Line Modules
1)
1)
1)
Line Connection Booksize
2-7