External Clock Ad Trigger - ICP DAS USA ET-7H16M Series User Manual

Table of Contents

Advertisement

3.1.2.

External clock AD trigger

In this trigger, send a start command from PC over the Ethernet to PET-7H16M to start the
acquisition. The A/D conversion is started actually when the external clock signal is input. The AI
value converted to digital data followed the external clock sampling rate and the data
accumulated to a network packet size returns to the PC. The process is stopped until a stop
command is sent over the Ethernet.
The frequency of the external clock can range from 1~30K Hz.
There are parameters below that need to be specified:
Scan channels
The trigger mode is external clock AD trigger
CON1
AI0
...
AI7
External
Clock
Trig
PET-7H16M Series User Manual, version 1.0.1
Sampling
PGA
Hold
FIFO
Memory
ADC
DMA
Ethernet
P.33