3.6

Calculation of the maximum cable length

Intrinsically safe power supply device STAHL 9160/13-11-11 (order code HA011405)
Technical data for EE300Ex
Supply voltage:
Max. current:
Technical data for STAHL 9160/13-11-11
Nominal operating voltage:
Input voltage for transmitter:
Max. load:
Calculation of maximum cable length of intrinsically safe input isolator
Cable 0.75mm²
(0.01in
)
2
Load resistance (load):
Input voltage for transmitter:
Min. supply voltage EE300Ex:
Maximum voltage drop on cable:
Total cable resistance:
Transform in accordance with L
Caution: this is the max. length without allowing for the intrinsic safety.
(cable capacity and inductivity may reduce the length even further)
3.7

Selecting a suitable power supply device for ATEx zone concept:

Example for evidence of the intrinsic safety in accordance with EN60079-14:2008 12.2.5.2,
EN60079-25:2010 13.1. CH1 and CH2 are galvanically separated, meaning the evidence of the
intrinsic safety can only be carried out using appropriate equipment.
Installation assumption:
Installing the EE300Ex (without display) in Zone 0
Connecting cable length:
Explosion group:
Temperature class:
Both electric circuits laid in one cable.
Intrinsically safe power supply device STAHL 9160/13-11-11
(Excerpt from the EC type approval test certificate)
Certified to:
II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc (certificate number: DMT 03 ATEX E 010 X)
II (1) D [Ex ia Da] IIIC (certificate number: DMT 03 ATEX E 010 X)
Entity parameters:
U
= 27V
0
I
= 88mA
0
P
= 576mW
0
C
IIC = 90nF
0
C
IIB = 705nF
0
L
IIC
= 2.3mH
0
L
IIB
= 17mH
0
(example):
total
300m
(984ft)
IIC
T4
20
U
= 9V + RL * 0.02A
Bin
I
max = 20mA
out
U
= 24V
N
U
= 16V
S
R
= 600Ohm
L
R
= 0.0267Ω/m
cable
R
= 200Ω
L
U
= 16V
S
U
= 9V + 200Ω * 0.02A = 13V
Bmin
U
= U
- U
= 16V – 13V = 3V
cable
S
Bmin
R
= R
* L
* 2
cable total
cable
total
U
= R
* I
drop
cable total
out max
= R
* L
* 2 * I
cable
total
L
= U
/ (I
* 2 * R
total
drop
out max
L
= 3V / (0.02A * 2 * 0.0267Ω/m )
total
L
= 2800m maximum cable length
total
(supply and return line)
=
out max
)
cable