Danfoss MCX-RTU User Manual page 23

Rooftop unit
Table of Contents

Advertisement

User Guide | MCX-RTU Rooftop
© Danfoss | ADAP-KOOL® | 2018.11
ALM
Parameters >
Function
Alarm Config
S03
Zone - Low Temp Zone Temp Low Alarm (0.0-40.0)
S04
Zone - Delay
Zone Temp Delay (0-240)
S05
CO2 - High Level
CO2 High Alarm (0-2000)
S06
CO2 - Delay
CO2 Alarm Delay (0-240)
S07
Fan High Run-
Fan High Daily Runtime (0-1500)
time
S08
Fan High Cycle
Fan High Daily Cycles (0-1000)
S09
Cool1 High
Cool 1 High Daily Runtime (0-1500)
Runtime
S10
Cool1 High Cycle Cool 1 High Daily Cycles (0-1000)
S11
Cool2 High
Cool 2 High Daily Runtime (0-1500)
Runtime
S12
Cool2 High Cycle Cool 2 High Daily Cycles (0-1000)
S13
Cool3 High
Cool 3 High Daily Runtime (0-1500)
Runtime
S14
Cool3 High Cycle Cool 3 High Daily Cycles (0-1000)
S15
Cool4 High
Cool 4 High Daily Runtime (0-1500)
Runtime
S16
Cool4 High Cycle Cool 4 High Daily Cycles (0-1000)
S17
Heat1 High
Heat 1 High Daily Runtime (0-1500)
Runtime
S18
Heat1 High Cycle Heat 1 High Daily Cycles (0-1000)
S19
Heat2 High
Heat 2 High Daily Runtime (0-1500)
Runtime
S20
Heat2 High Cycle Heat 2 High Daily Cycles (0-1000)
S21
Heat3 High
Heat 3 High Daily Runtime (0-1500)
Runtime
S22
Heat3 High Cycle Heat 3 High Daily Cycles (0-1000)
S23
Heat4 High
Heat 4 High Daily Runtime (0-1500)
Runtime
S24
Heat4 High Cycle Heat 4 High Daily Cycles (0-1000)
Default
Units
5.0
°C/°F
240
m
1000
ppm
15
m
1500
m
1000
1500
m
1000
1500
1000
1500
m
1000
1500
m
1000
1500
m
1000
1500
m
1000
1500
m
1000
1500
m
1000
RS8KE102 | 23