Danfoss MCX-RTU User Manual page 19

Rooftop unit
Table of Contents

Advertisement

User Guide | MCX-RTU Rooftop
© Danfoss | ADAP-KOOL® | 2018.11
COL
Parameters >
Function
Cool
Ct1
CL1 Target
Cool 1 Target Temperature (10.0-40.0°C)
Cb1
CL1 PreDelay
Cool 1 Pre Delay (0-240)
Ca1
CL1 PostDelay
Cool 1 Post Delay (0-240)
Ct2
CL2 Target
Cool 2 Target Temperature (10.0-40.0°C)
Cb2
CL2 PreDelay
Cool 2 Pre Delay (0-240)
Ca2
CL2 PostDelay
Cool 2 Post Delay (0-240)
Ct3
CL3 Target
Cool 3 Target Temperature (10.0-40.0°C)
Cb3
CL3 PreDelay
Cool 3 Pre Delay (0-240)
Ca3
CL3 PostDelay
Cool 3 Post Delay (0-240)
Ct4
CL4 Target
Cool 4 Target Temperature (10.0-40.0°C)
Cb4
CL4 PreDelay
Cool 4 Pre Delay (0-240)
Ca4
CL4 PostDelay
Cool 4 Post Delay (0-240)
CLr
CL Range +/-
Cool Range +/- (0.0-10.0K)
CL1
CL Ambient
Cool Mode Ambient Lockout (0.0-85.0°C)
Lockout
CL2
CL Lockout
Cool Mode Ambient Lockout Range +/-
Range +/-
(0.0-10.0K)
CnS
CL Night Setback Cool Mode Night Setback (0.0-30.0K)
Cs1
CL SupplyAir
Cool Mode Supply Air Target for VS Fan
(0.0-100.0°C)
Cm1
CL Min Fan
Cool Mode Min Fan Speed (0.0-100.0)
Speed
Cm2
CL Max Fan
Cool Mode Max Fan Speed (0.0-100.0)
Speed
CC1
CL Min Compr 1
Cool Min Compressor 1 Speed (0.0-100.0)
Speed
CC2
CL Min Compr 2
Cool Min Compressor 2 Speed (0.0-100.0)
Speed
CC3
CL Min Compr 3
Cool Min Compressor 3 speed (0.0-100.0)
Speed
CC4
CL Min Compr 4
Cool Min Compressor 4 speed (0.0-100.0)
Speed
CLi
PI Integ Time
CLg
PI Gain
Cns
CL Neutral SA
Rt1
HR1 Target
Heat Reclaim 1 Target Temperature (10.0-
40.0°C)
Default
Units
40.0
°C/°F
0
m
0
m
40.0
°C/°F
240
m
240
m
40.0
°C/°F
240
m
240
m
40.0
°C/°F
240
m
240
m
0.5
K/F
15.6
°C/°F
1.1
K/F
0.6
K/F
15.0
°C/°F
50.0
%
75.0
%
5.0
%
30.0
%
30.0
%
30.0
%
120
8.0
20.0
°C/°F
22.2
°C/°F
RS8KE102 | 19