Danfoss MCX-RTU User Manual page 18

Rooftop unit
Table of Contents

Advertisement

User Guide | MCX-RTU Rooftop
© Danfoss | ADAP-KOOL® | 2018.11
GEN
Parameters >
Function
General
y21
Avg RH1
Select RH1 sensor for Average(None/Local/
Glbl1-5)
y22
Avg RH2
Select RH2 sensor for Average(None/Local/
Glbl1-5)
y23
Avg RH3
Select RH3 sensor for Average(None/Local/
Glbl1-5)
y24
Not Used
Not Used
y25
Not Used
Not Used
y30
SelectExhaustFan
Select Exhaust Fan Schedule(0-16)
y31
Aux RO 1 Schedule
Select Aux RO 1 Schedule(0-16)
y32
Aux RO 2 Schedule
Select Aux RO 2 Schedule(0-16)
y33
Aux RO 3 Schedule
Select Aux RO3 Schedule(0-16)
y34
Aux RO 4 Sche-
Select Aux RO4 Schedule(0-16)
dule
y35
Enable Broadcast Enable Broadcast feature(No/Yes)
y36
Night Shutdown
Night Shutdown(No/Yes)
y37
Enable Logging
Enable Logging(No/Yes)
y38
Logging Interval
Set Logging Interval
FAN
Parameters >
Function
Fan
FN1
Fan Off Delay
Fan Off Delay (0-30)
FN2
Fan Proof Value
Fan Proof Value (0.0-100.0)
Used with the Fan CT AI . If AI is above this
value the is ON
FN3
Min Fan Speed
Min Fan Speed when in Fan Only Mode
(0.0-100.0)
FN4
Fan PI Gain
Fan PI Gain Value (0.0-100.0)
FN5
FanPIIntegrati-
Fan PI Integration Time (6-1000)
onTime
FN6
Building Press
Building Pressure Target(-1.00-1.00)
Target
FN7
OvrdFanSpeed
Stage One Fan Speed if exhaust fan one
enabled
FN8
OvrdFanHigh
Stage Two Fan Speed if exhaust fan two
enabled
FN9
Cond Target 1
Condenser Target
FNA
Cond Target 2
Condenser Target if Reheat enabled
Default
Units
None
None
None
0
0
0
0
0
Yes
No
No
1
m
Default
Units
2
m
2.0
a
30.0
%
5.0
60
0.00
350 PSI
bar/psi
400 PSI
bar/psi
RS8KE102 | 18