Danfoss MCX-RTU User Manual page 20

Rooftop unit
Table of Contents

Advertisement

User Guide | MCX-RTU Rooftop
© Danfoss | ADAP-KOOL® | 2018.11
HRC
Parameters >
Function
Heat Reclaim
Rb1
HR1 PreDelay
Heat Reclaim 1 Pre Delay (0-240)
Ra1
HR1 PostDelay
Heat Reclaim 1 Post Delay (0-240)
Rt2
HR2 Target
Heat Reclaim 2 Target Temperature (10.0-
40.0°C)
Rb2
HR2 PreDelay
Heat Reclaim 2 Pre Delay (0-240)
Ra2
HR2 PostDelay
Heat Reclaim 2 Post Delay (0-240)
Rt3
HR3 Target
Heat Reclaim 3 Target Temperature (10.0-
40.0°C)
Rb3
HR3 PreDelay
Heat Reclaim 3 Pre Delay (0-240)
Ra3
HR3 PostDelay
Heat Reclaim 3 Post Delay (0-240)
Rt4
HR4 Target
Heat Reclaim 4 Target Temperature (10.0-
40.0°C)
Rb4
HR4 PreDelay
Heat Reclaim 4 Pre Delay (0-240)
Ra4
HR4 PostDelay
Heat Reclaim 4 Post Delay (0-240)
HRr
HR Range +/-
Heat Reclaim Range +/- (0.0-10.0K)
HR1
HR Ambient
Heat Reclaim Mode Ambient Lockout (0.0-
Lockout
85.0°C)
HR2
HR Lockout
Heat Reclaim Mode Ambient Lockout
Range +/-
Range +/- (0.0-10.0K)
RnS
HR Night Set-
Heat Reclaim Mode Night Setback (0.0-
back
30.0K)
HRs
HR SupplyAir
Heat Reclaim Mode Supply Air Target for
VS Fan (0.0-100.0°C)
Rm1
HR Min Fan
Heat Reclaim Mode Min Fan Speed (0.0-
Speed
100.0)
Rm2
HR Max Fan
Heat Reclaim Mode Max Fan Speed (0.0-
Speed
100.0)
HET
Parameters >
Function
Aux Heat
Ht1
HT1 Target
Aux Heat 1 Target Temperature (10.0-
40.0°C)
Hb1
HT1 PreDelay
Aux Heat 1 Pre Delay (0-240)
Ha1
HT1 PostDelay
Aux Heat 1 Post Delay (0-240)
Ht2
HT2 Target
Aux Heat 2 Target Temperature (10.0-
40.0°C)
Hb2
HT2 PreDelay
Aux Heat 2 Pre Delay (0-240)
Ha2
HT2 PostDelay
Aux Heat 2 Post Delay (0-240)
Ht3
HT3 Target
Aux Heat 3 Target Temperature (10.0-
40.0°C)
Hb3
HT3 PreDelay
Aux Heat 3 Pre Delay (0-240)
Ha3
HT3 PostDelay
Aux Heat 3 Post Delay (0-240)
Ht4
HT4 Target
Aux Heat 4 Target Temperature (10.0-
40.0°C)
Hb4
HT4 PreDelay
Aux Heat 4 Pre Delay (0-240)
Ha4
HT4 PostDelay
Aux Heat 4 Post Delay (0-240)
HTr
HT Range +/-
Aux Heat Range +/- (0.0-10.0K)
HT1
HT Ambient
Aux Heat Mode Ambient Lockout (0.0-
Lockout
85.0°C)
HT2
HT Lockout
Aux Heat Mode Ambient Lockout Range
Range +/-
+/- (0.0-10.0K)
Default
Units
240
m
240
m
22.2
°C/°F
240
m
240
m
20.0
°C/°F
240
m
240
m
19.4
°C/°F
240
m
240
m
0.2
K/F
37.8
°C/°F
1.1
K/F
2.8
K/F
30.6
°C/°F
50.0
%
75.0
%
Default
Units
20.8
°C/°F
240
m
240
m
20.3
°C/°F
240
m
240
m
18.9
°C/°F
240
m
240
m
18.3
°C/°F
240
m
240
m
0.5
K/F
37.8
°C/°F
1.1
K/F
RS8KE102 | 20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents