User Guide | MCX-RTU Rooftop
© Danfoss | ADAP-KOOL® | 2018.11
To configure the controller, go to the Setup Options menu and make selections for your instal-
lation. Below is a list of the Setup Options along with their definitions.
OPT
Setup Options
Function
C01
Fan Type
Select Fan Type – Single Speed, Two Speed or
VariSpeed
C02
Fan Control Open
Select fan operation during Open periods –
Continuous or on Demand
C03
Fan Control Closed
Select fan operation during Closed periods –
Continuous or on Demand
C04
Fan Proof
Select Disable, DI or CT
C05
Monitor phase loss
Select No or Yes
C06
Cool Stages
Select number of cooling stages(0-4)
C07
CL1 Stage Size
Set size of cooling stage(0.0 – 2000.0)
C08
CL1 Stage Type
Select RO or AO
C09
CL2 Stage Size
Set size of cooling stage(0.0 – 2000.0)
C10
CL2 Stage Type
Select RO or AO
C11
CL3 Stage Size
Set size of cooling stage(0.0 – 2000.0)
C12
CL3 Stage Type
Select RO or AO
C13
CL4 Stage Size
Set size of cooling stage(0.0 – 2000.0)
C14
CL4 Stage Type
Select RO or AO
C15
Heat Reclaim
Select number of Heat Reclaim Stages(0-4)
Stages
C16
Aux Heat Stages
Select number of Aux Heat Stages(0-4)
C17
Use Gas Heat
Does Aux Heat use Gas Heat(Yes/No)
C18
Enable Dehumidi-
Enable Dehumidification(Yes/No)
fication
C19
Control Dehumid
Select Control Dehumidification with RH sensor
on
or CalcDP
C20
Reheat Cntl
Reheat Control(No, AuxRly,HeatReclaim,Both)
C21
Reheat Cntrl
Select Reheat Control Sensor(SupplyAir/Zone-
Sensor
Temp)
C22
Enable Damper
Enable Damper using(Disable, DO, or AO)
C23
Enthalpy Cntl
Enable Enthalpy Control(Yes/No)
C24
Free Cooling
Enable Free Cooling(Disable/Enable)
C25
CO2 Option
Select CO2 Damper Control(Disable, Monitor,
Control)
C26
Damper Cntrl
Select Damper control sensor(SupplyAir/Mixe-
Sensor
dAir)
C27
Enable HP Valve
Enable Heat Pump Valve in None, Heat or Cool
Mode
C28
Fan Control De-
For VS Fan, set fan to Off or Min when no
mand
demand
C29
Fan AO Type
Select AO Range for Fan(0-5,1-5,0-10,2-
10,Custom)
C30
Compr1 AO Type
Select AO Range for Cool1(0-5,1-5,0-10,2-
10,Custom)
C31
Compr2 AO Type
Select AO Range for Cool2(0-5,1-5,0-10,2-
10,Custom)
Default
Units
VS Fan
Continuous
Demand
DI
Yes
2
1000.0
AO
RO
RO
RO
2
2
Yes
Yes
CalcDP
HtRclm
SplyAir
AO
Yes
Enable
Control
SplyAir
None
Min
0-10
vdc
1-5
vdc
1-5
vdc
RS8KE102 | 15