Danfoss MCX-RTU User Manual page 16

Rooftop unit
Table of Contents

Advertisement

User Guide | MCX-RTU Rooftop
© Danfoss | ADAP-KOOL® | 2018.11
OPT
Setup Options
Function
C32
Compr3 AO Type
Select AO Range for Cool3(0-5,1-5,0-10,2-
10,Custom)
C33
Compr4 AO Type
Select AO Range for Cool4(0-5,1-5,0-10,2-
10,Custom)
C34
Damper AO Type
Select AO Range for Damper(0-5,1-5,0-10,2-
10,Custom)
C35
Custom AO Min
Set Min VDC for Custom AO(0.0-10.0vdc)
C36
Custom AO Max
Set Max VDC for Custom AO(0.0-10.0vdc)
C37
Ovrd Night Set-
If Yes, then Night Setback can be
back
overridden(Yes/No)
C42
Invert Fan AO
Invert Fan AO(Normal/Invert)
C43
Invert Compr 1 AO
Invert Compr1 AO(Normal/Invert)
C44
Invert Compr 2 AO
Invert Compr2 AO(Normal/Invert)
C45
Invert Compr
Invert Compr3 AO(Normal/Invert)
3 AO
C46
Invert Compr
Invert Compr4 AO(Normal/Invert)
4 AO
C47
Invert Damper
Invert Damper AO(Normal/Invert)
AO
C48
Zone RH
Select Sensor for Zone
RH(Disable,Local,GlobalRH1-5,Avg)
C49
Zone CO2
Select Sensor for Zone CO2(Disable,Local,
GlobalCO2-1-5)
C50
Outdoor Temp
Select Sensor for Outdoor
Temp(Disable,Local,Global)
C51
Outdoor RH
Select Sensor for Outdoor
RH(Disable,Local,Global)
C52
Outdoor CO2
Select Sensor for Outdoor
CO2(Disable,Local,Global)
C40
Supply Air
Select Sensor for Supply Air(Disable,Local)
Sensor
C39
Return Air
Select Sensor for Return Air(Disable, Local)
Sensor
C38
Mixed Air Sensor
Select Sensor for Mixed Air(Disable, Local)
C41
Zone Cntl Sensor Zone Control uses the Zone or Return Air
sensor
C53
HT/CL Ctrl Mode
Select HT/CL Ctrl Mode(Standard/Supply
Air)
C54
Fan VLT Modbus
Enable Fan VLT Modbus Control(Disable/
Enable)
C55
HTReset AO Type Select AO Range for HTReset AO(0-5,1-5,0-
10,2-10,Custom)
C56
Invert HTReset
Invert HTReset AO(Normal/Invert)
AO
C57
Zone Control
Zone Sensor
Config(Single;Average;High;Low)
C58
BldPress Sensor
Select Sensor for Building Pressure
Control(Disable;Local;Global)
C59
Condenser Cntl
Enable AO Condenser Control(No/Yes)
Default
Units
1-5
vdc
1-5
vdc
2-10
vdc
1.5
vdc
5.0
vdc
No
Normal
Normal
Normal
Normal
Normal
Normal
Local
Local
Local
Local
Disable
Local
Local
Local
Zone
Standard
Disable
0-10
Single
Local
No
RS8KE102 | 16