Next go to the Parameters menu for the screen below.
The table below shows all the parameters available to edit along with their definitions.
GEN
Parameters >
Function
General
y01
ON/OFF
Master Switch (Off/On)
y05
Temperature Units
Select Temperature/Pressure Units (C/F)
Also sets pressure to BAR when C used, PSI
when F used.
y06
Reset Runtime/
Reset Runtime/Cycle values (No/Yes), resets to
Cycle
No once values are cleared
y07
Reset to Default
Resets all settings to default values (No/Yes),
resets to No once values are set to default
y08
Night Setback
Can be used to put unit into night setback if
Select Schedule is zero. (Day/Night)
y27
Load Shed Value
Current Load Shed value from front end. (Read
Only)
y28
Load Shed Set
If Load Shed Value is above this setting, unit is
placed in Load Shed Mode (0-4, zero disables
load shed)
y26
Select Schedule
If Load Shed Value is above this setting, unit is
placed in Load Shed Mode (0-4, zero disables
load shed)
y29
Select Title24
Select which schedule in the front end the unit
will use for night setback.(0-16, zero disables
using front end schedule)
y09
Enable Alarms
Master Alarm Enable (No/Yes)
y10
Changeover Delay
Set delay time between switching between
Heat and Cool mode. (0-60)
y02
Enable Expansion
Enable Expansion Module (No/Yes)
y11
Enable AI Filters
Enable AI Filters (No/Yes)
y12
Global AI Filter
Set Global AI Filter Value (0, 2, 4, 16)
How many samples are used to average an AI
sensor.
y13
Startup Delay
Set power up delay before control starts. (5-600)
y14
MorningStartup-
Delay between Night Setback and Normal
Period
Mode(0-360
y15
Sensors Broadcast
Number of sensors to broadcast (Read Only)
y16
Broadcast Sensor 1
Select which sensor to broadcast as sensor 1
None/ZnRH1-ZnRH5/ZnCO21-ZnCO25/OtdTp/
OtdRH/OtdCO2
y17
Broadcast Sensor 2
Select which sensor to broadcast as sensor 2
None/ZnRH1-ZnRH5/ZnCO21-ZnCO25/OtdTp/
OtdRH/OtdCO2
y18
Broadcast Sensor 3
Select which sensor to broadcast as sensor 3
None/ZnRH1-ZnRH5/ZnCO21-ZnCO25/OtdTp/
OtdRH/OtdCO2
y19
Broadcast Sensor 4
Select which sensor to broadcast as sensor 4
None/ZnRH1-ZnRH5/ZnCO21-ZnCO25/OtdTp/
OtdRH/OtdCO2
y20
Broadcast Sensor 5
Select which sensor to broadcast as sensor 5
None/ZnRH1-ZnRH5/ZnCO21-ZnCO25/OtdTp/
OtdRH/OtdCO2
Default
Units
On
F
No
No
Day
--
0
0
0
Yes
5
m
No
Yes
16
600
s
360
m
None
None
None
None
None
RS8KE102 | 17