Mitsubishi Electric FR-A7AR Instruction Manual page 14

Relay output function
Hide thumbs Also See for FR-A7AR:
Table of Contents

Advertisement

INSTALLATION AND WIRING (FR-A700/F700 SERIES)
REMARKS
• Information on crimp terminals
Commercially available product examples (as of Jan. 2017)
Wire gauge
Terminal
screw size
(mm
0.3
M3
0.5
0.75
Crimping tool model No.: CRIMPFOX 6 (Phoenix Contact Co., Ltd.)
Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimping is
inappropriate, or the face is damaged.
(2) Loosen the terminal screw and insert the cable into the terminal.
Screw size
M3
CAUTION
• Undertightening can cause cable disconnection or malfunction. Overtightening can cause a short circuit or
malfunction due to damage to the screw or unit.
9
2
With insulation sleeve
)
AI 0,34-6TQ
AI 0,5-6WH
AI 0,75-6GY
Tightening torque
0.5Nm to 0.6Nm
Ferrule part No.
Without insulation sleeve
A 0,34-7
A 0,5-6
A 0,75-6
Damaged
Crumpled tip
Wire gauge
2
2
to 0.75mm
0.3mm
(Tip thickness: 0.4mm/tip width: 2.5mm )
Maker
Phoenix Contact
Co.,Ltd.
Unstranded
wires
Wires are not inserted
into the sleeve
Screwdriver
Small
flat-blade screwdriver

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a7ar e

Table of Contents