Installation Procedure - Mitsubishi Electric FR-A7AR Instruction Manual

Relay output function
Hide thumbs Also See for FR-A7AR:
Table of Contents

Advertisement

2.2

Installation Procedure

1)
Screw hole for
option mounting
(on earth plate)
Hex-head screw
for option mounting
REMARKS
• Remove a plug-in option after removing two screws on both left and right sides.
(When the plug-in option is mounted in the connector 3 (connector 1 for the FR-F
the plug-in option after removing a control circuit terminal block.)
INSTALLATION AND WIRING (FR-A700/F700 SERIES)
Screw hole for
option mounting
Inverter side
option
connector
3)
2)
4)
1)Remove the inverter front cover.
2)Mount the hex-head screw for option
mounting into the inverter screw hole
(on earth plate). (size 5.5mm,
tightening torque 0.56Nm to 0.75Nm)
3)Securely fit the connector of the plug-in
option to the inverter connector along
the guides.
4)Securely fix the both right and left sides
of the plug-in option to the inverter with
the accessory mounting screws.
(Tightening torque 0.33Nm to
0.40Nm) If the screw holes do not line-
up, the connector may not have been
plugged snugly. Check for loose
plugging.
Mounting
screws
700
series), it is easier to remove
2
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a7ar e