X111, X222, X333 Digital Inputs/Outputs - Siemens PPU 26x.3 series Manual

Ppu and components
Table of Contents

Advertisement

Connectable components
7.8 PP 72/48D PN and PP 72/48D 2/2A PN
LED status displays
For diagnostic purposes, the RJ45 sockets are each equipped with a green and a yellow LED.
This allows the following information on the respective PROFINET port to be displayed:
Name
Link
Activity
DIP switch S1
The correct logical IP address for communication (Page 239) with PLC I/O interface must be
assigned to the I/O module with the 10-bit DIP switch S1. The device name consists of the
PROFINET name and the device number: In the case of I/O modules, the 1st module is device
number 9.
Note
A newly set PROFINET address will only come into effect after a power OFF → ON.
The switch positions 9 and 10 guarantee the PROFINET functionality of the module and must
always be switched "ON".
1
2
3
4
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
ON
OFF
7.8.3.3

X111, X222, X333 digital inputs/outputs

Cable specification
50-pin ribbon cable connector:
● 50-pin insulation piercing connecting device with strain relief, ribbon cables and terminal
converter are required to connect the digital inputs and outputs.
● The required connecting cables (ribbon cables) must be provided by the user. The
maximum cable length is 30 m.
208
Color
Status
Green
Lit
Off
Yellow
Lit
Off
5
6
7
8
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Meaning
100 Mbit link available
Missing or faulty link
Sending or receiving
No activity
9
10
Device name
ON
ON
pp72x48pn9
pp72x48pn8
pp72x48pn7
pp72x48pn6
pp72x48pn5
Meaning
1st PP module
2nd PP module
3rd PP module
4th PP module
5th PP module
PPU and components
Manual, 10/2015, 6FC5397-2DP40-5BA3

Hide quick links:

Advertisement

Table of Contents
loading