TABLE
DISPLAY NAME
SERVICE
SERVICE
Brine Freeze Point
COMPRESSOR ENABLE
Enable Compressor A1
Enable Compressor A2
Enable Compressor A3
TABLE
DISPLAY NAME
SETPOINT
SETPOINT
COOLING
Cooling Setpoint 1
Cooling Setpoint 2
ICE Setpoint
RAMP LOADING
Cooling Ramp Loading
Brine Freeze Point
APPENDIX B — CCN TABLES (cont)
CCN SERVICE TABLES
RANGE
NNN.n
degF
Disable/Enable
Disable/Enable
Disable/Enable
CCN SETPOINT TABLES
RANGE
NNN.n
degF
NNN.n
degF
NNN.n
degF
N.n
NNN.n
degF
87
UNITS
POINT NAME
BRN_FRZ
ENABLEA1
ENABLEA2
ENABLEA3
UNITS
POINT NAME
CSP1
CSP2
CSP3
CRAMP
BRN_FRZ
DEFAULT
34.0
Unit Dependent
Unit Dependent
Unit Dependent
DEFAULT
44.0
44.0
32.0
1.0
34.0