Temperature Mode And Sub-Mode Directory; Pressures Mode And Sub-Mode Directory; Set Points Mode And Sub-Mode Directory; Inputs/Outputs Mode And Sub-Mode Directory - Carrier AquaSnap 30MPA Series Controls, Start-Up, Operation, Service, And Troubleshooting

Liquid chillers with scroll compressors and comfortlink controls
Hide thumbs Also See for AquaSnap 30MPA Series:
Table of Contents

Advertisement

ITEM
UNIT
ENT AND LEAVE UNIT TEMPS
CEWT
Cooler Entering Fluid
CLWT
Cooler Leaving Fluid
CDET
Condenser Entering Fluid
CDLT
Condenser Leaving Fluid
OAT
Outside Air Temperature
SPT
Space Temperature
DLWT
Lead/Lag Leaving Fluid
CIR.A
TEMPERATURES CIRCUIT A
SCT.A
Saturated Condensing Tmp
SST.A
Saturated Suction Temp
RGT.A
Compr Return Gas Temp
D.GAS
Discharge Gas Temp
SH.A
Suction Superheat Temp
ITEM
PRC.A
PRESSURES CIRCUIT A
DP.A
Discharge Pressure
SP.A
Suction Pressure
ITEM
EXPANSION
COOL
COOLING SETPOINTS
CSP.1
Cooling Setpoint 1
CSP.2
Cooling Setpoint 2
CSP.3
ICE Setpoint
HEAD
HEAD PRESSURE SETPOINTS
H.DP
Head Setpoint
FRZ
BRINE FREEZE SETPOINT
BR.FZ
Brine Freeze Point
ITEM
GEN.I
GENERAL INPUTS
STST
Start/Stop Switch
FLOW
Cooler Flow Switch
CD.FL
Condenser Flow Switch
DLS1
Demand Limit Switch 1
DLS2
Demand Limit Switch 2
ICED
Ice Done
DUAL
Dual Setpoint Switch
CRCT
CIRCUIT INPUTS
FKA1
Compressor A1 Feedback
FKA2
Compressor A2 Feedback
FKA3
Compressor A3 Feedback
HPS.A
High Pressure Switch A
4-20
4-20 MA INPUTS
DMND
4-20 ma Demand Signal
A.DL
Active Demand Limit
RSET
4-20 ma Reset Signal
D.RST
Degrees of Reset
CSP
4-20 ma Cooling Setpoint
ITEM
GEN.O
GENERAL OUTPUTS
C.LWP
Cooler Pump Relay
C.DWP
Condenser Pump
ALRM
Alarm State
CD.W.O*
Condenser Valve Open
CD.W.C*
Condenser Valve Close
* Not supported.
APPENDIX A — LOCAL DISPLAY TABLES (cont)

Temperature Mode and Sub-Mode Directory

EXPANSION

Pressures Mode and Sub-Mode Directory

EXPANSION

Set Points Mode and Sub-Mode Directory

RANGE
–20 to 70°F
–20 to 70°F
–20 to 32°F
85 to 120°F
–20 to 34°F
Inputs Mode and Sub-Mode Directory
EXPANSION
STRT/STOP
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
xx.x
xx.x
xx.x
Outputs Mode and Sub-Mode Directory
EXPANSION
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
UNITS
xxx.x °F
COOL_EWT
xxx.x °F
COOL_LWT
xxx.x °F
COND_EWT
xxx.x °F
COND_LWT
xxx.x °F
OAT
xxx.x °F
SPT
xxx.x °F
DUAL_LWT
xxx.x °F
TMP_SCTA
xxx.x °F
TMP_SSTA
xxx.x °F
TMP_RGTA
xxx.x °F
DISGAS
xxx.x ΔF
SH_A
UNITS
xxx.x PSIG
DP_A
xxx.x PSIG
SP_A
UNITS
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
UNITS
CCN POINT
START
COOLFLOW
CONDFLOW
DMD_SW1
DMD_SW2
ICE_DONE
DUAL_IN
K_A1_FBK
K_A2_FBK
K_A3_FBK
HPSA
LMT_MA
DEM_LIM
RST_MA
DEG_RST
CSP_IN
UNITS
CCN POINT
COOLPUMP
CONDPUMP
ALM
COND_WVO
COND_WVC
74
CCN POINT
COMMENT
CCN POINT
COMMENT
CCN POINT
DEFAULT
CSP1
44°F
CSP2
44°F
CSP3
32°F
HSP
95°F
BRN_FRZ
34°F
COMMENT
COMMENT