Operating Sequence; Operating Limitations; Service Test; Temperature Limits For Standard 30Mp Units - Carrier AquaSnap 30MPA Series Controls, Start-Up, Operation, Service, And Troubleshooting

Liquid chillers with scroll compressors and comfortlink controls
Hide thumbs Also See for AquaSnap 30MPA Series:
Table of Contents

Advertisement

Operating Limitations

TEMPERATURES — See Table 39 for 30MP standard
temperature limits. The 30MPW050-071 and 30MPA050-
071 units use different compressors that require different
operating envelopes. The 30MPW050-071 units (standard
condensing) use water-cooled optimized compressors,
which operate at lower condensing temperatures. The
30MPA050-071 units and 30MPW050-071 heat reclaim
units use air-cooled optimized compressors, which allow
for higher condensing temperatures.
CAUTION
Do not operate with cooler leaving chiller water (fluid)
temperature (LCWT) below 32 F (0° C) for standard units
with proper brine solution, 40 F (4.4 C) for the standard
units with fresh water, or below 15 F (–9.4 C) for units fac-
tory built for medium temperature brine, or unit damage
may occur.
High Cooler Leaving Chilled Water (Fluid) Temperatures
(LCWT) — During start-up with cooler the LCWT should not
be above approximately 60 F (16 C).
Low Cooler LCWT — For standard units with fresh water,
the LCWT must be no lower than 40 F (4.4 C). For standard
units with a proper brine solution, the LCWT must be no lower
than 32 F (0° C). If the unit is the factory-installed optional
medium temperature brine unit, the cooler LCWT can go
down to 15 F (–9.4 C).
Table 39 — Temperature Limits for
Standard 30MP Units
30MPW015-045,
30MPW050-071
TEMPERATURE LIMIT
CONDENSING
140
Maximum Condenser LWT
Minimum Condenser EWT
Maximum Cooler EWT*
Maximum Cooler LWT
Minimum Cooler LWT†
LEGEND
Entering Fluid (Water) Temperature
EWT —
Leaving Fluid (Water) Temperature
LWT —
*For sustained operation, EWT should not exceed 85 F (29.4 C).
†Unit requires modification below this temperature.
IMPORTANT: Medium temperature brine duty application
(below 32 F [0° C] LCWT) for chiller normally requires
factory modification. Contact your Carrier representative
for applicable LCWT range for standard water-cooled
chiller in a specific application.
VOLTAGE — ALL UNITS
Main Power Supply — Minimum and maximum acceptable
supply voltages are listed in the Installation Instructions.
Unbalanced 3-Phase Supply Voltage — Never operate a motor
where a phase imbalance between phases is greater than 2%.
To determine percent voltage imbalance:
% Voltage Imbalance = 100 x
The maximum voltage deviation is the largest difference
between a voltage measurement across 2 legs and the average
across all 3 legs.
30MPA,
STANDARD
30MPW050-071
HIGH
F
C
F
60
120
65
18
65
75
23
75
60
15
60
40
4
40
max voltage deviation
from avg voltage
average voltage
Example: Supply voltage is 240-3-60.
1. Determine average voltage:
Average voltage =
2. Determine maximum deviation from average voltage:
(AB) 243 – 239 = 4 v
(BC) 239 – 236 = 3 v
(AC) 239 – 238 = 1 v
Maximum deviation is 4 v.
3. Determine percent voltage imbalance:
% Voltage Imbalance = 100 x
This voltage imbalance is satisfactory as it is below the
maximum allowable of 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately. Do not operate unit until imbalance condition
is corrected.
Control Circuit Power — Power for the control circuit is
supplied from the main incoming power through a factory-
C
installed control power transformer (TRAN1) for all models.
49
Field wiring connections are made to the LVT.
18
23
15
The unit is started by putting the ENABLE/OFF/REMOTE
4
CONTROL switch in the ENABLE or REMOTE CONTROL
position. When the unit receives a call for cooling (either from
the internal control or CCN network command or remote con-
trol closure), the unit stages up in capacity to maintain the leav-
ing fluid set point. The first compressor starts 1
after the call for cooling.
For all units, if temperature reset is being used, the unit con-
trols to a higher leaving-fluid temperature as the building load
reduces. If demand limit is used, the unit may temporarily be
unable to maintain the desired leaving-fluid temperature be-
cause of imposed power limitations.
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during service. There may
be more than one disconnect switch. Tag all disconnect
locations to alert others not to restore power until work is
completed.
Service Test —
power must be on.
The Service Test function should be used to verify proper
operation of condenser output, compressors, minimum load
40
AB = 243 v
BC = 236 v
AC = 238 v
243 + 236 + 238
3
717
=
3
= 239
4
239
= 1.7%
OPERATION SEQUENCE