Carrier AquaSnap 30MPA Series Controls, Start-Up, Operation, Service, And Troubleshooting page 76

Liquid chillers with scroll compressors and comfortlink controls
Hide thumbs Also See for AquaSnap 30MPA Series:
Table of Contents

Advertisement

ITEM
EXPANSION
EXV.A
CIR A EXV CONFIGURATION
EXV.L
EXV Opening at Low LWT
LWT.L
LWT for EXV Min Opening
EXV.H
EXV Opening at High LWT
LWT.H
LWT for EXV Max Opening
MIN.A
EXV CIRC.A Min Position
RNG.A
EXVA Steps in Range
SPD.A
EXVA Steps Per Second
POF.A
EXVA Fail Position In%
MIN.A
EXVA Minimum Steps
MAX.A
EXVA Maximum Steps
OVR.A
EXVA Overrun Steps
TYP.A
EXVA Stepper Type
H.SCT
High SCT Threshold
X.PCT
Open EXV X% on 2nd COMP
X.PER
Move EXV X% on DISCRSOL
DELY
Lag Start Delay
L.DL.T
Low SH Delta T - EXV Move
SHR.T
EXV Rate Threshold
LEXM
Low SH Override EXV Move
CCN
CCN NETWORK CONFIGS
CCNA
CCN Address
CCNB
CCN Bus Number
BAUD
CCN Baud Rate
RSET
RESET COOL TEMP
CRST
Cooling Reset Type
MA.DG
4-20 - Degrees Reset
RM.NO
Remote - No Reset Temp
RM.F
Remote - Full Reset Temp
RM.DG
Remote - Degrees Reset
RT.NO
Return - No Reset Temp
RT.F
Return - Full Reset Temp
RT.DG
Return - Degrees Reset
DMDC
Demand Limit Select
DM20
Demand Limit at 20 mA
SHNM
Loadshed Group Number
SHDL
Loadshed Demand Delta
SHTM
Maximum Loadshed Time
DLS1
Demand Limit Switch 1
DLS2
Demand Limit Switch 2
LLEN
Lead/Lag Chiller Enable
MSSL
Master/Slave Select
SLVA
Slave Address
LLBL
Lead/Lag Balance Select
LLBD
Lead/Lag Balance Delta
LLDY
Lag Start Delay
PARA
Parallel Configuration
APPENDIX A — LOCAL DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
RANGE
0 to 50%
20 to 40 F
0 to 70%
20 to 70 F
0 to 100
0 to 65535
0 to 65535
0 to 100
0 to 65535
0 to 65535
0 to 65535
0 = UNIPOLAR
1 = BIPOLAR
50 to 140
0 to 30
0 to 30
0 to 100
0 to 240
–1.0 to 1.0F
0.4 to 3.0
1 to 239
0 to 239
1 = 2400
2 = 4800
3 = 9600
4 =19,200
5 =38,400
0 = No Reset
1 = 4 to 20 mA Input
2 = Outdoor Air
Temp
3 = Return Fluid
4 = Space Temp
–30 to 30F
0 to 125°F
0 to 125°F
–30 to 30F
0 to 30F
0 to 10F
–30 to 30F
0 = None
1 = Switch
(Requires EMM)
2 = 4 to 20 mA Input
(Requires EMM)
3 = CCN Loadshed
0 to 100
0 to 99
0 to 60
0 to 120
0 to 100
0 to 100
0 to 239
0 = Master Leads
1 = Slave Leads
2 = Automatic
40 to 400 hours
0 to 30 minutes
UNITS
XX%
XX° F
XX%
XX° F
XXX
XXXXX
XXXXX
XXX
XXXXX
XXXXX
XXX
0,1
XXX
XX
XX
XXX
XXX
XX.X F
X.X%
XXX
CCNADD
XXX
CCNBUS
X
CCNBAUDD
X
CRST_TYP
XX.XΔF
MA_DEG
REM_NO
XXX.X °F
XXX.X °F
REM_FULL
XX.X ΔF
REM_DEG
XXX.XΔF
RTN_NO
XXX.XΔF
RTN_FULL
XX.XΔF
RTN_DEG
X
DMD_CTRL
XXX%
DMT20MA
XXX
SHED_NUM
SHED_DEL
XXX%
SHED_TIM
XXX
XXX%
DLSWSP1
XXX%
DLSWSP2
DSBL/ENBL
LL_ENA
SLVE/MAST
MS_SEL
XXX
SLV_ADDR
X
LL_BAL
XXX
LL_BAL_D
XXX
LL_DELAY
NO/YES
PARALLEL
76
CCN POINT
DEFAULT
25%
10 F
50%
35 F
2
3690
150
0
0
3690
167
1
115
10
5
10
6
0.2F
1.0%
1
0
3 = 9600
0 = No Reset
10.0F
10.0F
0.0F
0.0F
10F
0.0F
0.0F
0 = None
100
0
0
60
80
50
DSBL
MAST
0
0 = Master Leads
168
5 minutes
YES