Service Test Mode And Sub-Mode Directory - Carrier AquaSnap 30MPA Series Controls, Start-Up, Operation, Service, And Troubleshooting

Liquid chillers with scroll compressors and comfortlink controls
Hide thumbs Also See for AquaSnap 30MPA Series:
Table of Contents

Advertisement

ITEM
EXPANSION
TEST
SERVICE TEST MODE
OUTS
OUTPUTS AND PUMPS
CLR.P
Cooler Pump Relay
CND.P
Condenser Pump
UL.TM
Comp A1 Unload Time
CC.H
Crankcase Heater
CW.VO
Condenser Valve Open
CW.VC
Condenser Valve Close
EXV.A
EXV% Open
LL.SV
Liquid Line Solenoid
RMT.A
Remote Alarm Relay
CMPA
CIRCUIT 1 COMPRESSOR TST
CC.A1
Compressor A1 Relay
UL.TM
Comp A1 Unload Time
CC.A2
Compressor A2 Relay
CC.A3
Compressor A3 Relay
MLV
Minimum Load Valve Relay
APPENDIX A — LOCAL DISPLAY TABLES (cont)

Service Test Mode and Sub-Mode Directory

RANGE
0 to 15
0 to 15
UNITS
CCN POINT
OFF/ON
MAN_CTRL
OFF/ON
S_CLPMP
OFF/ON
S_CNDPMP
xx
S_A1ULTM
OFF/ON
S_CCH
OFF/ON
S_CWVO
OFF/ON
S_CWVC
xxx%
S_EXV_A
OFF/ON
S_LLSV
OFF/ON
S_ALM
OFF/ON
S_A1_RLY
xx
S_A1ULTM
OFF/ON
S_A2_RLY
OFF/ON
S_A3_RLY
OFF/ON
S_MLV
73
COMMENT
To enable Service Test
mode, move Enable/Off/
Remote control switch to
OFF. Change TEST to
ON. Move switch to
ENABLE.
not supported
not supported