Carrier R080-528 Installation Instructions Manual

Air-cooled chillers, 60 hz

Advertisement

Quick Links

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-72
Step 1 - Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . 1
Step 2 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 1
Step 3 - Piping Connections . . . . . . . . . . . . . . . . . . . 44
• GENERAL
Duplex Chiller Control Configuration . . . . . . . . . . . . 53
Step 5 - Install Accessories . . . . . . . . . . . . . . . . . . . . 72
• ELECTRICAL
Step 6 - Leak Test Unit . . . . . . . . . . . . . . . . . . . . . . . . . 72
Step 7 - Refrigerant Charge . . . . . . . . . . . . . . . . . . . . 72
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can
be hazardous due to system pressures, electrical components,
and equipment location. Only trained, qualified installers and
service mechanics should install, start up, and service this
equipment.
When working on the equipment, observe precautions in the
literature, and on tags, stickers, and labels attached to the
equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling, rigging, and setting bulky equipment.
ELECTRIC SHOCK HAZARD
To avoid the possibility of electrical shock,
open and tag all disconnects before install-
ing this equipment.
INTRODUCTION
These instructions cover installation of 30GXN,R080-528
liquid chillers with electronic controls and units with
factory-installed options (FIOPs).
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 903
Catalog No. 533-00053
Book 2
Tab
5c
ECOLOGIC™ Air-Cooled Chillers

Installation Instructions

Page
Printed in U.S.A.
30GXN,R080-528
IMPORTANT: This equipment generates, uses, and can
radiate radio frequency energy. If not installed and used
in accordance with these instructions, this equipment
may cause radio interference. The equipment has been test-
ed and found to comply with the limits of a Class A
computing device as defined by the FCC (Federal Commu-
nications Commission, U.S.A.) Regulations, Subpart J of
Part 15, which are designed to provide reasonable protec-
tion against such interference when operated in a commer-
cial environment.
INSTALLATION
Step 1 - Inspect Shipment -
age upon arrival. If damage is found, immediately file a claim
with the shipping company. When considering location for the
unit, be sure to consult NEC (National Electrical Code, U.S.A.)
and/or local code requirements. Allow sufficient space for air-
flow, wiring, piping, and service as follows.
Front and Rear . . . 6 ft (1829 mm); from outer most edge*
Top . . . . . . . . . . . . . . . . . . . . . . . Do not restrict in any way
Ends . . . . . . . . . . . . 5 ft (1524 mm); from outer most edge*
*Outer most edge may include sound enclosure or hail
guard.
See Fig. 1-25 for unit dimensions and Table 1 for duplex
unit combinations. Ensure surface beneath unit is level and
capable of supporting the operating weight of the unit. See
Fig. 26-28 and Tables 2A-2D for unit mounting and operating
weights. Unit operating ranges are listed in Tables 3A and 3B.
Step 2 - Rig and Place Unit -
signed for overhead rigging and it is important that this method
be used. See Fig. 28 or rigging label on unit. Holes are provid-
ed in frame baserails; field-supplied 2-in. Schedule 40 pipes
pass through these holes, extending beyond frame far enough
to attach cables or chains on both sides.
As shown in Fig. 28, use the recommended length of chain
or cable to facilitate lifting of the unit. Two options have been
provided for the rigging of these units.
IMPORTANT: Rigging option 1 must be used for
30GXN,R204-350 and associated modular units. Sizes
080-178 and associated modular units may use either rig-
ging option 1 or 2.
Rigging option 1 uses a central rigging point. The lifting
point must be a minimum of 13 ft (3.9 m) above the top of the
unit. For a more level lift, the chains or cables of the cooler/
compressor side must be shortened by about 20 in. (508 mm).
Use spreader bars to keep cables or chains clear of unit sides.
As further protection for the coil faces, leave plywood sheets
supplied for shipping in place against sides of unit, behind
cables or chains. Option 1 must be used for 30GXN,R204-350,
and applicable modular units.
Form 30GXN,GXR-3SI
Pg 1
60 Hz
Inspect unit for dam-
These units are de-
6-03
Replaces: 30GXN,GXR-2SI

Advertisement

Table of Contents
loading

Summary of Contents for Carrier R080-528

  • Page 1: Table Of Contents

    INTRODUCTION cables or chains. Option 1 must be used for 30GXN,R204-350, These instructions cover installation of 30GXN,R080-528 and applicable modular units. liquid chillers with electronic controls and units with factory-installed options (FIOPs).
  • Page 2: Installation

    Rigging option 2 (size 080-178 units) uses an offset lifting Do not point load the base rail of the unit. If point loading is bar. The bar must be at least 8 ft (2.5 m) above the top of the required (i.e., for spring isolators) the base rail must be support- unit to reduce the risk of damage to the unit.
  • Page 28 99 in. (2515) 6 in. (152) CONTROL 30GXN,R 080,090 85 1/8 in. (2162) 113 3/8 in. (2879) WEIGHT DISTRIBUTION, ALUMINUM-FIN UNITS — lb (kg) WEIGHT DISTRIBUTION, COPPER-FIN UNITS — lb (kg) DISTRIBUTION POINTS DISTRIBUTION POINTS UNIT UNIT 30GXN,R 30GXN,R 1384 2686 1355 1486...
  • Page 29 153 3/16 in. (3891) 106 in. (2692) 6 in. (152) 30GXN,R 118,128,138,150,160, CONTROL 85 1/8 in. 283B, 303B, 370B, (2162) 373B, 415B 167 5/16 in. (4250) WEIGHT DISTRIBUTION, ALUMINUM-FIN UNITS — lb (kg) WEIGHT DISTRIBUTION, COPPER-FIN UNITS — lb (kg) DISTRIBUTION POINTS DISTRIBUTION POINTS UNIT...
  • Page 30 244 1/16 in. (6199) 169 3/4 in. (4312) 97 1/16 in. (2466) 22 3/4 in. (578) CONTROL 30GXN, R 163, 178, 85 1/8 in. (2162) 303A, 328A, 353A/B 266 15/16 in. (6780) WEIGHT DISTRIBUTION, ALUMINUM-FIN UNITS — lb (kg) WEIGHT DISTRIBUTION, COPPER-FIN UNITS — lb (kg) DISTRIBUTION POINTS DISTRIBUTION POINTS UNIT...
  • Page 31 208 1/16 in. (5285) 173 11/16 in. (4412) 107 1/2 in. (2731) 58 1/2 in. (1486) 22 3/4 in. (578) CONTROL 30GXN,R 204,225, 85 1/8 in. 370A, 450A/B, 475B (2162) 231 in. (5867) WEIGHT DISTRIBUTION, ALUMINUM-FIN UNITS — lb (kg) DISTRIBUTION POINTS UNIT 30GXN,R...
  • Page 32 280 1/16 in. (7114) 229 7/8 in. (5839) 166 11/16 in. (4233) 130 3/16 in. (3307) 73 1/16 in. (1856) 22 3/4 in. (578) CONTROL 30GXN,R 208,228 85 1/8 in. 453A, 453B, 478B (2162) 303 1/4 in. (7703) WEIGHT DISTRIBUTION, ALUMINUM-FIN UNITS — lb (kg) DISTRIBUTION POINTS UNIT 30GXN,R...
  • Page 33 219 11/16 in. (5580) 169 3/4 in. (4312) 97 1/16 in. (2465) 47 11/16 in. (1211) 22 3/4 in. (578) CONTROL 30GXN,R 249,264, 85 1/8 in. 390A, 415A, 475A, (2162) 500A/B, 525A/B 267 1/4 in. (6788) WEIGHT DISTRIBUTION, ALUMINUM-FIN UNITS — lb (kg) DISTRIBUTION POINTS UNIT 30GXN,R...
  • Page 34 316 1/8 in. (8030) 265 13/16 in. (6752) 215 1/2 in. (5474) 179 7/16 in. (4558) 130 1/8 in. (3305) 73 in. (1854) 22 11/16 in. (525) 85 1 /8 in. 30GXN,R 253, 268-350, 373A, 393A, 418A, (2162) 478A, 503A/B, 528A/B 339 1/32 in.
  • Page 35 2.00 6.00 (50.8) (152.4) MINIMUM 4.00 (101.6) Ø1.00 24.00 0.296 (25.4) (609.6) (7.52) MINIMUM 1.58 (38.71) NOTE: Dimensions are in inches. Dimensions in ( ) are in millimeters. Fig. 27 — Recommended Mounting with Base Rail Plate...
  • Page 36 CENTER OF GRAVITY 13' MINIMUM (3982 mm) CENTER GRAVITY CONTROL CONTROL COOLER/ COMPRESSOR COOLER/ SIDE COMPRESSOR SIDE RIGGING OPTION 2 RIGGING OPTION 1 30GXN,R080-160 AND ASSOCIATED MODULAR UNITS CENTER OF GRAVITY MAXIMUM SHIPPING MAXIMUM SHIPPING LIFTING HOLES (See Note 5) WEIGHT WITHOUT WEIGHT WITH UNIT...
  • Page 37 30GXN,R153, 163, 174, 178 AND ASSOCIATED MODULAR UNITS MAXIMUM SHIPPING MAXIMUM SHIPPING LIFTING HOLES CENTER OF GRAVITY WEIGHT WITHOUT WEIGHT WITH UNIT PACKAGING PACKAGING 30GXN,R 153, 283A, 328B, 393B, 9,446 4285 10,446 4738 82.0 2083 99.0 2515 35.0 106.0 2692 418B 153, 283A, 328B, 393B,...
  • Page 38 30GXN,R204-350 AND ASSOCIATED MODULAR UNITS LIFTING HOLES CENTER OF GRAVITY SHIPPING WEIGHT SHIPPING WEIGHT UNIT WITHOUT PACKAGING WITH PACKAGING 30GXN,R 12,426 5636 13,426 6 090 57.8 1467 40.3 1024 67.7 1720 114.6 2910 34.6 13,826 6271 14,826 57.8 1467 40.3 1024 67.7 1720...
  • Page 39 Table 2A — Physical Data, 60 Hz Units — English UNIT SIZE 30GXN,R OPERATING WEIGHT (lb) Cu-Al 6313 6907 6333 7201 7514 7662 7524 8649 7553 8664 7714 8789 8784 9,684 9,072 6988 7602 7008 7896 8209 8357 8219 9699 8248 9714 8414...
  • Page 40 Table 2B — Physical Data, 60 Hz Duplex Units — English UNIT SIZE 30GXN,R OPERATING WEIGHT (lb) HFC-134a Cu-Al 18,473 19,068 19,978 20,588 21,769 25,525 21,617 26,420 22,974 Cu-Cu 20,823 21,686 23,046 23,924 24,194 29,680 24,017 31,025 25,774 REFRIGERANT CHARGE Circuits Qty Module A Ckt A/Ckt B (lb) 263/178...
  • Page 41 Table 2C — Physical Data, 60 Hz Units — SI UNIT SIZE 30GXN,R OPERATING WEIGHT (kg) Cu-Al 2863 3133 2872 3266 3408 3475 3413 3923 3426 3930 3499 3987 3984 4393 4115 Cu-Cu 3169 3448 3179 3582 3724 3791 3728 4399 3741 4406...
  • Page 42 Table 2D — Physical Data, 60 Hz Duplex Units — SI UNIT SIZE 30GXN,R OPERATING WEIGHT (kg) HFC-134a Cu-Al 8379 8649 9 062 9 339 9 874 11 578 9 805 11 984 10 421 Cu-Cu 9445 9837 10 454 10 852 10 974 13 463...
  • Page 43 **For applications requiring cooler entering water temperature operation at less 4. Where winds of 5 mph (2.2 m/s) or greater are anticipated at outdoor ambient than 45 F (7.2 C), contact your local Carrier representative for unit selection us- temperatures below 32 F (0° C), wind baffles are required.
  • Page 44: Step 3 - Piping Connections

    Table 3B — Duplex Unit Operating Range MAX. COOLER TEMPERATURE REFERENCE NOMINAL NO. OF DIFFERENCE MIN FLOW RATE FLOW RATE 30GXN,R COOLER PASSES 11.1 20.8 41.5 11.1 21.9 43.8 11.1 24.1 48.2 11.1 26.5 53.0 11.1 31.7 55.5 11.1 28.0 56.1 11.1 37.1...
  • Page 45: Brine Units

    Table 5 — Flexible Coupling Alignment MAX. PARALLEL MAX. MAX. MAX. WORKING PIPE SIZE LENGTH CONNECTION MODEL OFFSET ELONGATION COMPRESSION PRESSURE in. (mm) in. (mm) STYLE in. (mm) in. (mm) in. (mm) Flex-Hose SVG8 8 (219) 16 (406) 0.5 (13) Victaulic/Varies Unaflex Style 1000 8 (219)
  • Page 46 3. All wiring must comply with applicable local and national codes. Airflow Through Air-Handling Unit 4. All piping must follow standard piping techniques. Refer to Carrier System Design Man- Power Wiring ual or appropriate ASHRAE (American Society of Heating, Refrigeration, and Air Condi- Chilled Water Piping tioning Engineers) handbook for details.
  • Page 47 Airflow Through Air-Handling Unit 3. All wiring must comply with applicable local and national codes. 4. All piping must follow standard piping techniques. Refer to Carrier System Design Man- Power Wiring ual or appropriate ASHRAE (American Society of Heating, Refrigeration, and Air Condi- Chilled Water Piping tioning Engineers) handbook for details.
  • Page 48 Assume Victaulic Style 77 connections at all joints For all models: A pipe is 8″ x length shown below; B pipe is 8″ x length shown below C is Flexhose 8 x 16 SVG, 16″ (406.4 mm) long Weight: 23.5 lbs (10.7 kg) Size ‘A’...
  • Page 49 The 30GXN,R units should be installed using certified drawings. LEGEND 2. Refer to Carrier System Design Manual for details regarding piping techniques. 3. Piping, switches, valves, vent, gages, strainers, drain, and vibration isolation Field Piping are all field supplied.
  • Page 50: Step 4 - Make Electrical Connections

    Step 4 — Make Electrical Connections — For units with 380-3-60 power: Control voltage is tapped from line to neutral. No additional power supply is required. If electrical characteristics of the available power supply must a separate power source is required, disconnect the wires be- agree with the unit nameplate rating.
  • Page 51: Duplex Unit Power Connections

    DUPLEX UNIT POWER CONNECTIONS — The 30GXN,R polyethylene. An aluminum/polyester 100% foil shield and an duplex units will require separate power supplies to each mod- outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with ule for both main power and control power. Power should be a minimum operating temperature range of –20 C to 60 C is provided according to the requirements for each module (see required.
  • Page 52 COMMUNICATIONS WIRING LEGEND NOTES: 1. Power for control circuit should be supplied from a separate source through a field- — Alarm supplied disconnect (see Tables 7A-7E for maximum current protection requirements). — Chilled Water Pump Connect control circuit power to terminals 1 and 2 of TB4. Control circuit conductors for CWPI —...
  • Page 53: Duplex Chiller Control Configuration

    Duplex Chiller Control Configuration — address (CCNA, Configuration mode under OPT2). In addi- tion, the chillers must reside on the same CCN bus. The master Fig. 36-39 and Table 6. The dual chiller routine is available for chiller controls the slave chiller by changing its mode (STAT, the control of two units supplying chiller fluid on a common control mode) and its operating setpoint (CTPT, control point).
  • Page 54 Table 7A — Electrical Data Reduced Ambient 115 F Data UNIT VOLTAGE STANDARD CONDENSER FAN CONTROL CIRCUIT POWER UNIT Supplied SUPPLY Rec Fuse Size V-Hz # Power Supply V-Hz 30GXN,R MOCP MCA and MOCP QTY. REQD (3 Ph) Conductors (Single Ph) 208/230-60 356.5 527.9...
  • Page 55 Table 7A — Electrical Data Reduced Ambient 115 F Data (cont) UNIT VOLTAGE STANDARD CONDENSER FAN CONTROL CIRCUIT POWER UNIT Supplied SUPPLY Rec Fuse Size V-Hz # Power Supply V-Hz MCA and 30GXN,R MOCP QTY. REQD (3 Ph) Conductors (Single Ph) MOCP 208/230-60 527.7...
  • Page 56 Table 7A — Electrical Data Reduced Ambient 115 F Data (cont) UNIT VOLTAGE HIGH-STATIC CONDENSER FAN CONTROL CIRCUIT POWER UNIT Supplied # Power Rec Fuse Size SUPPLY V-Hz V-Hz MCA and 30GXN,R Supply MOCP QTY. REQD (3 Ph) (Single Ph) MOCP Conductors 208/230-60...
  • Page 57 Table 7A — Electrical Data Reduced Ambient 115 F Data (cont) UNIT VOLTAGE HIGH-STATIC CONDENSER FAN CONTROL CIRCUIT POWER UNIT Supplied # Power Rec Fuse Size SUPPLY V-Hz V-Hz MCA and 30GXN,R Supply MOCP QTY. REQD (3 Ph) (Single Ph) MOCP Conductors 208/230-60...
  • Page 58 Table 7B — Electrical Data High Ambient 125 F Data, Standard Condenser Fan UNIT VOLTAGE STANDARD CONDENSER FAN CONTROL CIRCUIT POWER UNIT Supplied SUPPLY Rec Fuse Size V-Hz # Power Supply V-Hz MCA and 30GXN,R MOCP QTY. REQ’D (3 Ph) Conductors (Single Ph) MOCP*...
  • Page 59 Table 7B — Electrical Data High Ambient 125 F Data, Standard Condenser Fan (cont) UNIT VOLTAGE STANDARD CONDENSER FAN CONTROL CIRCUIT POWER UNIT Supplied SUPPLY Rec Fuse Size V-Hz # Power Supply V-Hz MCA and 30GXN,R MOCP QTY. REQ’D (3 Ph) Conductors (Single Ph) MOCP*...
  • Page 60 Table 7C — Electrical Data High Ambient 125 F Data, Duplex Units (Standard Condenser Fan) UNIT VOLTAGE STANDARD CONDENSER FAN CONTROL CIRCUIT POWER UNIT Supplied SUPPLY Rec Fuse Size V-Hz # Power Supply V-Hz MCA and 30GXN,R MOCP QTY. REQ’D (3 Ph) Conductors (Single Ph)
  • Page 61 Table 7D — Electrical Data High Ambient 125 F Data, High-Static Condenser Fan UNIT VOLTAGE HIGH-STATIC CONDENSER FAN CONTROL CIRCUIT POWER UNIT Supplied SUPPLY Rec Fuse Size V-Hz # Power Supply V-Hz MCA and 30GXN,R MOCP QTY. REQD (3 Ph) Conductors (Single Ph) MOCP*...
  • Page 62 Table 7D — Electrical Data High Ambient 125 F Data, High-Static Condenser Fan (cont) UNIT VOLTAGE HIGH-STATIC CONDENSER FAN CONTROL CIRCUIT POWER UNIT Supplied SUPPLY Rec Fuse Size V-Hz # Power Supply V-Hz MCA and 30GXN,R MOCP QTY. REQD (3 Ph) Conductors (Single Ph) MOCP*...
  • Page 63 Table 7E — Electrical Data High Ambient 125 F Data, Duplex Units (High-Static Condenser Fan) UNIT VOLTAGE HIGH-STATIC CONDENSER FAN CONTROL CIRCUIT POWER UNIT Supplied SUPPLY Rec Fuse Size V-Hz # Power Supply V-Hz MCA and 30GXN,R MOCP QTY. REQD (3 Ph) Conductors (Single Ph)
  • Page 64 Table 7E — Electrical Data High Ambient 125 F Data, Duplex Units (High-Static Condenser Fan) (cont) UNIT VOLTAGE HIGH-STATIC CONDENSER FAN CONTROL CIRCUIT POWER UNIT Supplied SUPPLY Rec Fuse Size V-Hz # Power Supply V-Hz MCA and 30GXN,R MOCP QTY. REQD (3 Ph) Conductors (Single Ph)
  • Page 65 Table 8A — Compressor Electrical Data (High Ambient) COMPRESSOR COMPRESSOR NAMEPLATE NAMEPLATE UNIT SIZE UNIT SIZE V-Hz V-Hz 30GXN,R 30GXN,R (3 Phase) (3 Phase) 208/230-60 208/230-60 230-60 230-60 460-60 74.4 580.0 61.6 485.0 460-60 102.6 820.0 70.6 580.0 080-XL 108-XL 575-60 60.3 484.0...
  • Page 66 Table 8A — Compressor Electrical Data (High Ambient) (cont) COMPRESSOR COMPRESSOR NAMEPLATE NAMEPLATE UNIT SIZE UNIT SIZE V-Hz V-Hz 30GXN,R 30GXN,R (3 Phase) (3 Phase) 208/230-60 208/230-60 230-60 230-60 460-60 124.4 920.0 102.6 820.0 460-60 124.4 920.0 151.3 1175.0 135-XL 160-XL 575-60 98.8...
  • Page 67 Table 8A — Compressor Electrical Data (High Ambient) (cont) COMPRESSOR NAMEPLATE UNIT SIZE V-Hz 30GXN,R (3 Phase) 208/230-60 230-60 460-60 151.3 1175.0 73.1 580.0 124.4 920.0 204-XL 575-60 120.6 940.0 57.7 484.0 98.8 736.0 380-60 183.4 1299.0 87.2 641.0 150.0 1017.0 208/230-60 334.7...
  • Page 68 Table 8A — Compressor Electrical Data (High Ambient) (cont) COMPRESSOR NAMEPLATE UNIT SIZE V-Hz 30GXN,R (3 Phase) — — 208/230-60 230-60 — — 264-XL 460-60 151.3 1175.0 151.3 1175.0 151.3 1175.0 — — 575-60 120.6 940.0 120.6 940.0 120.6 940.0 —...
  • Page 69 Table 8B — Compressor Electrical Data (Reduced Ambient) COMPRESSOR COMPRESSOR UNIT NAMEPLATE UNIT NAMEPLATE SIZE V-Hz SIZE V-Hz 30GXN,R (3 Phase) 30GXN,R (3 Phase) 208/230-60 208/230-60 230-60 230-60 460-60 70.6 580.0 59.0 485.0 460-60 93.6 820.0 75.7 685.0 080-XL 118-XL 575-60 56.5 484.0...
  • Page 70 Table 8B — Compressor Electrical Data (Reduced Ambient) (cont) COMPRESSOR NAMEPLATE UNIT SIZE V-Hz 30GXN,R (3 Phase) 208/230-60 230-60 208-XL 460-60 108.7 920.0 108.7 920.0 93.6 820.0 575-60 87.0 736.0 87.0 736.0 74.9 656.0 380-60 131.5 1017.0 131.5 1017.0 113.3 906.0 208/230-60 240.2...
  • Page 71 Table 9 — Condenser Fan Electrical Data STANDARD/LOW NOISE CONDENSER FAN HIGH STATIC CONDENSER FAN NAMEPLATE VOLTAGE UNIT 30GXN,R (V-Hz) (3-Phase) Total Quantity FLA (ea) Total Quantity FLA (ea) 208/230-60 14.6 230-60 14.6 080, 090 460-60 575-60 380-60 208/230-60 14.6 083, 093, 108 230-60 14.6...
  • Page 72: Step 5 - Install Accessories

    R-134a only. DO NOT USE ANY OTHER refrigerant in lation unless a leak was detected in Step 6 — Leak Test Unit these units. section. If dehydration and recharging is necessary, use indus- try standard practices or refer to Carrier Standard Service Tech- niques Manual as required.
  • Page 74 CALL FOR FREE CATALOG 1-800-644-5544 [ ] Packaged Service Training [ ] Classroom Service Training Copyright 2003 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 903 Catalog No.

This manual is also suitable for:

Ecologic 30gxn

Table of Contents