Graco Therm-O-Flow 25C994 Instructions Manual page 4

Communications gateway module. installation kit
Table of Contents

Advertisement

Installation
3. Connect the CAN cable that you removed from the
ADM to the available splitter connection on the back
of the electrical control panel. Run that cable
through the same opening as the other CAN cable.
CAN Cable
from Splitter
CAN Cable from ADM
F
. 3: CAN Cable Connection
IG
4. Connect the two cables to the CGM connectors.
Either cable can be connected to either connector.
CAN Connector 1
F
. 4: CGM Connectors
IG
5. Attach the two ferrite suppressors included in the kit
to the ends of the two cables closest to the CGM.
6. Use the adhesive cable tie included in the kit to
attach the CAN cables to the back of the control
box.
4
Opening Leading to CGM
CAN Connector 2
7. Connect the Ethernet, DeviceNet, or PROFIBUS
cable to the CGM as applicable. Connect the other
end of the cable to the fieldbus device.
F
. 5: Connecting the Fieldbus
IG
8. Perform the Install or Update Data Map procedure
in Communications Gateway Module Instructions -
Parts, manual 312864.
9. See the Available Internal Data on page 9 for
details on the fieldbus pinout setup.
10. Perform Setup on page 5 to configure the fieldbus.
Fieldbus Connection
3A5186B