Siemens SINAMICS S120 Equipment Manual page 87

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Table 3- 10
Technical specifications for Basic Line Modules, 380 V – 480 V 3 AC, part 2
Order number
Infeed power
- Rated power Pn at 400 V 3 AC
- Pmax at 400 V 3 AC
DC link current
- Rated current I
n_DC
- Base load current I
H_DC
- Maximum current I
max_DC
Input current
- Rated current at 400 V 3 AC
- maximum
Supply voltages
- Line voltage
- Line frequency
- Electronics power supply
- Fan supply voltage
- DC link voltage
Power requirements
- Electronics power consumption
(24 V DC)
- Fan power consumption
(230 V AC)
Max. ambient temperature
- Without derating
- With derating
DC link capacitance
- Basic Line Module
- Drive line-up, max.
Efficiency
Power loss, max.
Cooling air requirement
Sound pressure level
L
(1 m) at 50/60 Hz
pA
Line/load connection
Max. connection cross-sections
- Line connection (U1, V1, W1)
- DC link connection (DCP, DCN)
- PE connection
Max. cable length
(total of all motor cables and DC link)
- shielded
- unshielded
Degree of protection
Dimensions
- Width
- Height
- Depth
Frame size
Chassis power units
Manual, (GH3), 10/2008, 6SL3097-2AE00-0BP3
6SL3330–
1TE41–5AA0
kW
710
kW
1065
A
1500
A
1170
A
2250
A
1265
A
1897
V
380 V 3 AC -10 % (-15 % < 1 min) to 480 V 3 AC +10 %
ACrms
Hz
V
DC
V
AC
V
1.35 x U
DC
A
1.1
A
4.5
°C
40
°C
55
µF
29000
µF
232000
η
0.992
kW
5.5
m
/s
0.36
3
dB(A)
71 / 73
M12
mm²
6 x 185
mm²
6 x 185
mm²
4 x 240
m
4000
m
6000
IP00
mm
310
mm
1653
mm
550
GB
3.2 Basic Line Modules
47 to 63 Hz
24 (20.4 - 28.8)
230 (195.5 - 264.5)
(partial load) / 1.32 x U
line
Flat connector for screw
Line Modules
(full load)
line
87