Table 4- 16
Technical specifications for Motor Module, 510 V DC – 720 V DC, Part 2
Order number
Output current
- Rated current I
n
- Base load current I
L
- Base load current I
H
- for S6 operation (40 %) I
- Max. output current I
max
Unit rating
1)
- Power on basis of I
n
- Power on basis of I
H
Rated DC link current
for power supplied via
- Basic/Smart Line Module
- Active Line Module
Supply voltages
- DC link voltage
- Electronics power supply
- Output voltage
Rated pulse frequency
- Max. pulse frequency without derating
- Max. pulse frequency with derating
Max. ambient temperature
- Without derating
- With derating
DC link capacitance
Power requirements
- Electronics power consumption (24 V DC)
- Fan supply, 400 V 2 AC, 50/60 Hz
Power loss, max.
Cooling air requirement
Sound pressure level
L
(1 m) at 50/60 Hz
pA
DC link/motor connection
Max. conductor cross-sections
- DC link connection (DCP, DCN)
- Motor connection (U2, V2, W2)
- PE connection PE1
- PE connection PE2
Max. motor cable length
shielded / unshielded
Degree of protection
Dimensions
- Width
- Height
- Depth
Chassis power units
Manual, (GH3), 10/2008, 6SL3097-2AE00-0BP3
6SL3320–
A
A
A
A
S6
A
kW
kW
A
A
V
DC
V
DC
V
ACrms
kHz
kHz
kHz
°C
°C
μF
A
A
kW
m
/s
3
dB(A)
mm²
mm²
mm²
mm²
m
mm
mm
mm
1TE35–0AA0
1TE36–1AA0
1TE35–0AA3
1TE36–1AA3
490
605
477
590
438
460
540
--
715
885
250
315
200
250
588
726
530
653
24 (20.4 – 28.8)
0 to 0.72 x DC link voltage
2
1.25
2
1.25
8
5
40
40
55
55
9600
12600
1.2
1.0
1.6 / 2.4
3.2
4.5
5.84
0.36
0.78
< 69
< 72
Flat connector for screws
M10
M12
2 x 185
Busbar
2 x 185
4 x 240
2 x 185
1 x 240
2 x 185
2 x 240
300 / 450
300 / 450
IP20
IP00
326
503
1533
1475
545
540
Motor Modules
4.6 Technical specifications
1TE37–5AA0
1TE38–4AA0
1TE37–5AA3
1TE38–4AA3
745
840
725
820
570
700
--
---
1087
1230
400
450
315
400
894
1008
805
907
510 to 720
1.25
1.25
1.25
1.25
5
5
40
40
55
55
15600
16800
1.0
1.0
3.2
3.2
6.68
7.15
0.78
0.78
< 72
< 72
M12
M12
Busbar
Busbar
4 x 240
4 x 240
1 x 240
1 x 240
2 x 240
2 x 240
300 / 450
300 / 450
IP00
IP00
503
503
1475
1475
540
540
167