740/760 Series Initial Power-Up

SU MO TU
WE TH FR SA DAYS
Time & Day
Regen Time & Day
Salt
Capacity
Hardness
32
Rev A
Regeneration Cycles:
C1 – Backwash
C2 – Regeneration Draw/Slow Rinse (not used in filter mode)
C3 – Slow Rinse (not used in filter mode)
C4 – System Pause (to repressurize tank)
C5 – Fast Rinse cycle 1
C6 – Backwash cycle 2 (not used in filter mode)
C7 – Fast Rinse cycle 2 (not used in filter mode)
C8 – Regenerant Refill (not used in filter mode)
Initial Power Up – (Camshaft proceeds to HOME position)
At initial power-up, the camshaft may need to rotate to the HOME (in
service position).
Camshaft may take 1 to 2 minutes to return to HOME position.
Err 3 will be displayed until the camshaft returns to HOME position.
If more than 2 minutes elapses, verify that the motor is turning the
camshaft. If it is not turning, contact Dealer.
NOTE:
The 700 Series controller features a self-test sequence. At first power-
up of the control, you may see a number such as 1.00, 1.02, 1.04, or 2.00
displayed. This is an indication that the self-test is not completed. To complete
the test, verify that the turbine cable is connected. Blow air into the turbine port
(valve outlet) to spin the turbine. The controller will verify that the turbine works
and the self-test will finish. Proceed with the initial start-up procedure.