Signal connections
Direct connection: with solid bare wire or flexible wire for cross-section 0.2 mm
AWG 14 to 24 or flexible wire with end sleeves for cross-section 0.25 mm
AWG 16 to 23. By using a wire for a less cross-section (min. AWG 26), the wire has to be
connected to the terminal block by a practical facility (end sleeve).
Please use copper conductors only!
For 7XV5662-0AD00, use lines with twisted double cores and additional shield for the
connection between the network termination and the CC-2M. The impedance must be 120 Ω
in the E1 mode and 100 Ω in the T1 mode. Connect the shield on both sides. The data cable
must be at least a cable of the type S/UTP (Screen Unshielded Twisted Pair). An S/UTP
cable consists of a plastic cable sheath and an overall shielding around the twisted double
core pairs. The shielding may consist of copper braiding, of aluminum foil, or of both. You
can also use cables of the type S/FTP (Screen Foil Twisted Pair) where the twisted double
core pairs are additionally shielded with metallic foils.
For the 7XV5662_0AD01, you must use coaxial cables with a characteristic impedance of
75 Ω. Preferably use preconfigured cables for G.703 E1 connections.
The arrangement of the connection at the screw-type terminals of the CC-2M is shown in the
following table.
Cable pair
Transmiter
Receive
Table 5
Connections E1/T1 interface of the CC-2M
Voltage connections and GOK relay
Direct connection: with solid bare wire or flexible wire for cross-section 0.2 mm
AWG 14 to 24 or flexible wire with end sleeves for cross-section 0.25 mm
AWG 16 to 22.
Please use copper conductors only!
Earthing connection
Use a solid, low-impedance and low-inductance business earthing and put these together with
at least a M4 screw. Mass and earthing ribbons DIN 72333, form A. Connect the ribbon with the
protection conductor of the switchboard or the cupboard .
C53000-B1174-C205-2
7XV5662-0AD00
Signal
Tx tip
Tx ring
Rx tip
Rx ring
Terminal
Tx a
Tx b
Rx a
Rx b
English
2
to 2.5 mm
2
to 1.5 mm
7XV5662-0AD01
Signal
Tx
Tx
Rx
Rx
2
to 2.5 mm
2
to 1.5 mm
2
,
2
,
2
,
2
,