Siemens 7XV5662-0AD00/DD Directions For Use Manual page 61

Communication converter 2m
Table of Contents

Advertisement

Available languages

Available languages

7XV5662-0AD00/DD, 7XV5662-0AD01/DD
Protection
Device 1
FO
Protection
Device 2
FO
Figure 28 Typical structure of a communication line with splitting frames
The following table shows the assignment of the individual interfaces in the E1 frame and T1
frame. The time slots are counted for the E1 frame from 0 to 31 and for the T1 frame from 1
to 24.
Standard
Time slots for
FO1/LWL1
E1
3, 7, 11, 14, 18,
22, 26, 30
T1
3, 6, 9, 12, 15, 18,
21, 24
Tabelle 7 Time slots
The following figure shows the jumpers of E1/T1 interface
For 7XV6552-0AD01, these jumpers are not equipped, as in the unbalanced mode, only the
E1 standard is specified.
On delivery, the jumpers E1, B8ZS, and ESF are plugged in.
C53000-B1174-C205-2
CC-2M
FO1/
LWL1
E1/T1
FO2/
LWL2
Time slots for
FO2/LWL2
2, 6, 10, 13, 17,
21, 25, 29
2, 5, 8, 11, 14,
17, 20, 23
PDH Network
DIV
Time slots for
RS232/RS485
4, 8, 12, 15, 19,
23, 27
4, 7, 10, 13, 16,
19, 22
CC-2M
FO1/
FO
LWL1
E1/T1
FO2/
LWL2
CC-2M
FO1/
FO
LWL1
E1/T1
FO2/
LWL2
not used
5, 9, 20, 24, 28,
31
-
English
Protection
Device 1
Protection
Device 2
61

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

7xv5662-0ad01/dd

Table of Contents