Kalor Ada 28B User Manual page 11

Boiler stove
Table of Contents

Advertisement

Connection to the flue pipe
The flue pipe must have internal dimensions not
larger than 20x20 cm, or diameter 20 cm. In the
event of larger dimensions, or of the flue pipe
being in poor condition ( for example cracks,
poor insulation, etc.), it is advisable to fit a
stainless steel pipe of suitable diameter inside
the flue pipe throughout its length, right up to
the top.
Check with suitable instruments that there is a
draught between 6 Pa and 10 Pa. This type of
connection ensures the evacuation of the fumes
even in the event of a temporary power cut.
At the bottom of the flue pipe, provide an
inspection cap to allow periodic checking and
cleaning, which must be done annually. Make
a gas-tight connection to the flue pipe, using
pipes and connectors as recommended by us.
You must ensure that a windproof cowl should
be fitted which complies with the standards in
force
Connection to an external flue with insulated
or double-wall pipe
The only type of pipe which is permissible is
insulated (double-walled) stainless steel, smooth
on the inside, fixed to the wall. Flexible stainless
steel pipe must not be used. At the bottom of
the flue pipe, provide an inspection cap to allow
periodic checking and cleaning, which must be
done annually. Make a gas-tight connection to
the flue pipe, using pipes and connectors as
recommended by us. You must ensure that a
windproof cowl should be fitted which complies
with the standards in force.
Check with suitable instruments that there is a
draught between 6 Pa and 10 Pa.
Connection to the flue pipe
For proper functioning, the connecting pipe
between the stove and the chimney or flue duct
must have a slope of not less than 3% in the
horizontal stretches, the length of which must
not exceed 2 metres and the vertical distance
between one tee connector and another (change
of direction) must not be less than 1,5 m.
Check with suitable instruments that there is a
draught between 6 Pa and 10 Pa. At the botton of
the flue pipe, provide an inspection cap to allow
periodic checking and cleaning, which must be
done annually.
Make a gas-tight connection
to the flue pipe, using pipes and connectors as
recommended by us. You must ensure that a
windproof cowl should be fitted which complies
with the standards in force.
Fig. 2: connection to the
flue pipe.
Fig.
3:
connection
to
external flue with insulated or
double-wall pipe.
an
59

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sonia 28b

Table of Contents