Utilization Of The Guard Terminal (Model 6503) - AEMC 6501 User Manual

Megohmmeter
Hide thumbs Also See for 6501:
Table of Contents

Advertisement

4.5
C
Guard terminals are useful when measuring high resistance values
and for stabilizing readings.
When testing the insulation at the end of a cable, it is necessary to
eliminate the error from surface leakage which occurs, particularly
at high resistance values. The purpose of the guard terminal is to
provide a third terminal within the path of the surface leakage "D".
Connect the instrument as shown in Figure 4-1.
If there is no shield at "B", use a copper wire wound several times
around the exposed surface "B". (Note: If a shield is not available
and you do not make up a shield around "B" and connect to the
guard terminal (-), the measurement will be erroneous and lead to
confusion as to the cable's state.)
Megohmmeter Models 6501/6503
Shop for AEMC products online at:
Utilization of the Guard Terminal
D
B
G
Figure 4-1
ShopAEMC
www.
(Model 6503)
A
A = Insulation
B = Shield
C = Conductor
D = Exposed surface