4.3.3
In time resistance reading (Dielectric Absorption Ratio), readings
are taken at 30 seconds and 60 seconds to obtain the dielectric
absorption ratio.
Insulation resistance @ 60s
Insulation resistance @ 30s
This test is useful to increase the accuracy of spot testing. In gen-
eral, a ratio of 1.25:2 or better should be required. A ratio below this
indicates that repair is probably needed.
Remember that a DC insulation test may be used for acceptance
testing, but is more commonly used to check the gradual deteriora-
tion of equipment over its life. Consult your equipment manufacturer
for specific test or test voltage if not known.
Insulation resistance decreases with moisture, temperature and age
and should be recorded over time at a given temperature and cor-
rected.
4.4
• Check with the equipment manufacturer for factory insula-
• Do not rely on insulation resistance testing alone as proof
• Do not expect the same value for all parts of all machines.
• Observe consistent test time duration, recognizing that
• Correct all readings properly to a standard reference tem-
• Know what you are testing. Isolate the piece of equipment
• Watch trends rather than relying on single "spot" readings.
14
Shop for AEMC products online at:

Ratio Testing

= Dielectric Absorption ratio
Successful Insulation Resistance Testing
tion resistance readings.
of winding conditions.
total current through insulation under test will vary with
time.
perature (see IEEE std #43-2000, Temperature Correction
Curve).
from other circuitry.