  • Page 1 Operating Guide AK-SM 800...
  • Page 2 Operating Guide | AK-SM 800 Overview When replacing a generic device on an AK-SM 800 system, issues are seen which leads to additional time spent during this replacement process. Typical issues are: 1. Duplicate addresses 2. Uncfg messages shown 3. *Mismatch* shown 4.
  • Page 3 3. Setup the new device correctly: Note: the correct EDF file for the new device MUST be installed! Change the configuration file to the correct one and confirm that the ‘Mismatch’ message is gone. © Danfoss | DCS (vt) | 2019.09 AQ314725020974en-000101 | 3...
  • Page 4 ‘Uncfg’ is gone after having installed the correct EDF file and reconfigured the new device. 5. Reset system: The above flow is executed via StoreView Desktop. It is also possible to complete these steps using the local screen interface. © Danfoss | DCS (vt) | 2019.09 AQ314725020974en-000101 | 4...