Quick Installation Guide
00825-0200-4101, Rev EA
June 2010
European Certifications
I1
ATEX Intrinsic Safety
Certification No. Baseefa08ATEX0129X
Ex ia IIC T4 (T
IP66
1180
Table 1. Input Parameters
U
= 30V
i
I
= 300 mA
i
P
= 1.3 W
i
C
= 0 µF
i
Special Conditions for Safe Use (X):
The device is not capable of withstanding the 500V insulation test required by Clause 6.3.12
of EN60079-11. This must be taken into account when installing the apparatus.
IA
ATEX FISCO Intrinsic Safety
Certification No. Baseefa08ATEX0129X
Ex ia IIC T4 (T
IP66
1180
Table 2. Input Parameters
U
= 17.5 V
i
I
= 380 mA
i
P
= 5.32 W
i
=  5 µF
C
i
= 10 µH
L
i
Special Conditions for Safe Use (X):
The device is not capable of withstanding the 500V insulation test required by Clause
Clause 6.3.12 of EN60079-11. This must be taken into account when installing the
apparatus.
N1 ATEX Type n
Certification No. Baseefa08ATEX0130X
Ex nAnL IIC T4 (T
U
= 32 Vdc max
i
IP66
Special Conditions for Safe Use (X):
The device is not capable of withstanding the 500V insulation test required by Clause 6.8.1
of EN60079-15. This must be taken into account when installing the apparatus.
= –60 to +60 °C)
amb
= –60 to +60 °C)
amb
= –40 to +70 °C)
amb
II 1 G
II 1 G
II 3 G
Rosemount 2051