Ul Ratings - Emerson xm678d Operation And Installation Manual

Controllers for multiplexed cabinets wuth interior stepper driver
Hide thumbs Also See for xm678d:
Table of Contents

Advertisement

21 UL Ratings

Evaporator Fan:
120 V, 50/60 Hz, 1/4 HP, 30k cycles
125 V, 50/60 Hz, 1/3 HP, 6k cycles
250 V, 50/60 Hz, 1/2 HP, 30k cycles
Compressor:
120 V/240 V, D300 Pilot Duty, 30k cycles
Auxiliary (not populated in XM66 series):
120/240 V, 50/60 Hz, 5 A, General Purpose, 6k cycles
120/240 V, 50/60 Hz, 3 A, Resistive, 100k cycles
Light:
Relay Outputs 
120 V, 50/60 Hz, 5 A, General Purpose, 6k cycles, 
UL Ratings
120 Vac, 1000 W Tungsten, 6k cycles
240 Vac, 1400 W Tungsten, 6k cycles
Defrost:
120/240 V, 50/60 Hz, 10A, Resistive, 30k cycles
120/240 V, 50/60 Hz, C300, Pilot Duty, 30k cycles
Alarm (not populated on XM66 series):
120/240 V, 50/60 Hz, 5 A, General Purpose, 6k cycles
120/240 V, 50/60 Hz, 3 A, Resistive, 100k cycles
Stepper Valve (24 V models only):
24 V, 0.9 A maximum
Table 21-1- XM678D UL Ratings
Temperature - Maximum ambient operating temperature 60°C
Pollution Degree - 2 (Normally only nonconductive pollution. However, a temporary conductivity caused by
condensation may be expected.)
Overvoltage Category - III
Software Class: A
Maximum Phase to Ground Voltage: 120 Vac
38 • XM678D I&O Manual
Ratings
Terminal
Terminals 9 and 10
Terminals 11 and 12
Terminals 18 and 17
Terminals 16 and 15
Terminals 14 and 13
Terminals 1, 2 and 3
Terminals 45 to 49
026-1219 Rev 3