Alarm Recovery - Emerson xm678d Operation And Installation Manual

Controllers for multiplexed cabinets wuth interior stepper driver
Hide thumbs Also See for xm678d:
Table of Contents

Advertisement

Display
17
PAL
Pressure switch lock i1F, i2F o i3F = PAL.
Minimum operating pressure threshold from
18
LOP
LOP parameter.
Maximum operating pressure threshold from
19
MOP
MOP parameter.
Low superheating from LSH parameter and
20
LSH
SHd delay.
High superheating from HSH parameter and
21
HSH
SHd delay.
22
rtC
Clock settings lost.
23
rtF
Clock damaged.
24
EE
EEPROM serious problem.
25
Err
Error with upload/download parameters.
26
End
Parameters have been correctly transferred.
Table 17-1 - Display Messages

17.1. Alarm Recovery

Probe alarms P1, P2, P3, and P4 start some seconds
after the fault in the related probe; they automatically
stop some seconds after the probe restarts normal
operation. Check the connections before replacing the
probe.
Temperature alarms HA, LA, HA2, and LA2
automatically stop as soon as the temperature returns
to normal values.
Alarms EA and CA (with i1F = bAL) recover as soon
as the digital input is disabled. Alarm CA (with 
i1F = PAL) recovers only by switching OFF and ON
the device.
Alarm Recovery
Causes
ELECTRONIC VALVE ALARM
CLOCK ALARM
OTHERS
Notes
All the outputs are OFF.
The valve output increases its opening of dML
quantity every second.
The valve output decreases its opening of dML
quantity every second.
The valve will be closed; the alarm will be
showed after SHd delay.
Only display.
Defrost will be performed with IdF till restoring
the settings of RTC.
Defrost will be performed with IdF.
Output OFF.
Repeat the operation.
Display Messages • 31