24 Default Parameter Map

The first column numbers are simple indexes not related to the position on the device menu. The total amount
of parameters can be different depending on the applications. SUBMENUS: V1...V30 ELECTRONIC VALVE
belongs to EEV.
Label
Value
EEU
FtY
290
Table 24-1 - Default Parameter Map
44 • XM678D I&O Manual
Description
ELECTRONIC
VALVE
Type of gas used by plant. Fundamental parameter for correct
functioning of all system.
LABEL
Kind of gas
Range
By pressing SET you can enter the
electronic expansion valve submenu.
REFRIGERANT
R22
r22
134
r134A
290
r290 – Propane
404
r404A
47A
r407A
47C
r407C
47F
r407F
410
r410A
448
r448A
449
r449A
450
r450A
507
r507
513
r513A
CO2
r744 - Co2
Notes
OPERATING
RANGE
-58 to 120°F/
-50 to 60°C
-58 to 120°F/
-50 to 60°C
-58 to 120°F/
-50 to 60°C
-94 to 120°F/
-70 to 60°C
-58 to 120°F/
-50 to 60°C
-58 to 120°F/
-50 to 60°C
-58 to 120°F/
-50 to 60°C
-58 to 120°F/
-50 to 60°C
-69 to 120°F/
-45 to 60°C
-69 to 120°F/
-45 to 60°C
-69 to 120°F/
-45 to 60°C
-94 to 120°F/
-70 to 60°C
-69 to 120°F/
-45 to 60°C
-58 to 120°F/
-50 to 60°C