14.1. Synchronized Defrost

The synchronized defrost allows multiple defrosts to
be managed from different boards connected through
the LAN connection. In this way, the boards can
perform simultaneous defrosts with the possibility to
end them in a synchronized manner.
CAUTION! In this case, the Adr parameter
cannot be duplicated because defrost cannot be
managed correctly.
BEGIN
Find Adr
Modify
or
Adr
EXIT
Table 14-2 - Synchronized Defrost Keys
The LSn and LAn parameter are used only to show
the actual settings (read only). See Figure 14-2 for an
example of configuration:
Figure 14-2 - Configuration Example
14.1.1. Daily Defrost From RTC: [EdF =
rtC]
• IdF Parameter: For safety reason, force the value
of Idf at +1 with respect to the interval between the
two Ld 
parameters. The IdF timer is restarted after defrost
Synchronized Defrost
Press for three (3) seconds,
the EEU or other will be
showed. The measurement
unit blinks.
Press the down arrow key
several times to find the
Adr parameter, then press
SET.
Set the value of Adr
parameter, then press SET
to confirm the parameter.
Press both keys to exit
from menu or wait for
about 10 seconds.
and at every power ON.
• DEFROST START: At the time selected by the
parameters Ld1 to Ld6 or Sd1 to Sd6.
• DEFROST END: If the probes reach the dtE
temperature or for maximum MdF time.
• SAFETY and RtC or RtF ALARM: With clock
alarm, the device will use the parameters IdF, dtE
and MdF.
CAUTION! Do not set [EdF = rtC] and
[CPb = n].
• MULTIMASTER DEFROST: All the probes with
clock
Unit A
Par
(RTC)
Adr
n
N + 1
9 hours
IdF
9 hours safety
safety
MdF
45 min safety
45 min safety
dtE
12°C safety
12°C safety
Ld1
06:00 1°
06:00 1°
Ld2
14:00 2°
14:00 2°
Ld3
22:00 3°
22:00 3°
Table 14-3 - Multimaster Defrost Example
Multimaster Function Menu (SEC) • 25
Unit B
Unit C
(RTC)
(RTC)
N + 2
9 hours safety
45 min safety
12°C safety
06:00 1°
14:00 2°
22:00 3°