Building Or Wall On One Side Of Unit; Case 1 For Awv 008-010 Models - Daikin Pathfinder AWV Series Installation, Operation And Maintenance Manual

Air-cooled screw chillers 100 to 565 tons (350 to 1985 kw) hfc-134a refrigerant 60/50 hz
Table of Contents

Advertisement

Case 1: Building or Wall on One Side of Unit
For all models, maintain a 4 foot minimum from a wall of any
height; however, performance may be affected at this distance
due to air recirculation and elevated condenser pressure.
Assuming all service clearance requirements are met,
to
Figure 9
depict Case 1 performance adjustments as the wall
height and distance increases.
Figure 4: Building or Wall on One Side of Unit
Height
Distance
of
Between
Wall
Wall
and
Unit
Figure 5: Case 1 for AWV 008-010 Models
% Full Load Capacity Reduction (AWV008-010)
1.2%
1.0%
0.8%
0.6%
0.4%
0.2%
0.0%
8
12
% Full Load Power Increase (AWV008-010)
2.5%
2.0%
1.5%
1.0%
0.5%
0.0%
8
12
www.DaikinApplied.com
Figure 5
Control Panel
16
20
Height of Wall - Feet
16
20
Height of Wall - Feet
I
nsTallaTIon and
Figure 6: Case 1 for AWV012-014 Models
% Full Load Capacity Reduction (AWV012-014)
1.2%
1.0%
0.8%
0.6%
0.4%
0.2%
0.0%
8
% Full Load Power Increase (AWV012-014)
2.5%
2.0%
1.5%
1.0%
0.5%
0.0%
8
4 Feet
Figure 7: Case 1 for AWV016-018
% Full Load Capacity Reduction (AWV016-018)
5 Feet
1.4%
6 Feet
1.2%
1.0%
0.8%
24
0.6%
0.4%
0.2%
0.0%
4 Feet
8
5 Feet
% Full Load Power Increase (AWV016-018)
6 Feet
3.0%
2.5%
24
2.0%
1.5%
1.0%
0.5%
0.0%
8
9
IOM 1242-2 • PATHFINDER
a
C
pplICaTIon
onsIderaTIons
12
16
20
Height of Wall - Feet
12
16
20
Height of Wall - Feet
12
16
20
Height of Wall - Feet
12
16
20
Height of Wall - Feet
MODEL AWV CHILLERS
®
4 Feet
5 Feet
6 Feet
24
4 Feet
5 Feet
6 Feet
24
4 Feet
5 Feet
6 Feet
24
4 Feet
5 Feet
6 Feet
24