Circuit Level Set Points
The settings in this section all exist for each individual circuit.
Table 39: Set Points for Individual Circuits
Description
Mode, Enabling, Configuration
Circuit Mode
Capacity Control
Manual Speed
Condenser Control
Condenser Temp Target Max
Fan Staging Deadbands
Sensor Offsets
Evap Pressure Offset
Cond Pressure Offset
Oil Pressure Offset
Economizer Pressure Offset
Suction Temp Offset
Discharge Temp Offset
Economizer Temp Offset
Administrative and Service Support
Clear Cycle Timers
Service Pumpdown
Compressor Run Hours
Compressor Starts
Event Log - Event Selection
Event Log - Day Selection
NOTE: The Manual Speed value will follow the compressor speed command while Speed Control = Auto. When Speed Control
= Manual, the Manual Speed set point can be set to the desired value. Manual Speed set point should have a maximum
value equal to the Maximum Compressor Speed set point for that circuit.
Fan Staging Deadbands
Fan Stage Deadband settings will only be visible if Fan VFD Configuration is set to None or 1st Fan VFD. The condenser fan
staging deadbands have different default values based on the Fan VFD Configuration set point. When that set point is changed, a
set of default values for the fan staging deadbands is loaded as shown.
Table 40: Fan VFD Configuration = None
Set Point
Fan Stage Up Deadband 0
Fan Stage Up Deadband 1
Fan Stage Up Deadband 2
Fan Stage Up Deadband 3
Fan Stage Up Deadband 4
Fan Stage Up Deadband 5
Fan Stage Down Deadband 1
Fan Stage Down Deadband 2
Fan Stage Down Deadband 3
Fan Stage Down Deadband 4
Fan Stage Down Deadband 5
www.DaikinApplied.com
Default
Enable
Auto
See Note 1
50.0°C (122°F)
See
Table 40 and Table 41
0 kPa (0 psi)
0 kPa (0 psi)
0 kPa (0 psi)
0 kPa (0 psi)
0°C (0°F)
0°C (0°F)
0°C (0°F)
No
Off
0
0
Low Pressure Hold
Current
Default Value Loaded
4°C (7.2°F)
5°C (9°F)
5.5°C (9.9°F)
6°C (10.8°F)
6.5°C (11.7°F)
6.5°C (11.7°F)
10°C (18°F)
8°C (14.4°F)
5.5°C (9.9°F)
4°C (7.2°F)
4°C (7.2°F)
Range
Disable, Enable, Test
Auto, Manual
30.0°C to 55.0°C (86°F to 131°F)
1 to 10°C (1.8 to 18°F)
-100 to 100 kPa (-14.5 to 14.5 psi)
-100 to 100 kPa (-14.5 to 14.5 psi)
-100 to 100 kPa (-14.5 to 14.5 psi)
-100 to 100 kPa (-14.5 to 14.5 psi)
-5.0 to 5.0°C (-9.0 to 9.0°F)
-5.0 to 5.0°C (-9.0 to 9.0°F)
-5.0 to 5.0°C (-9.0 to 9.0°F)
No, Yes
Off, On
0 to 999999 hours
0 to 65535
Low Press Hold, Low Press Unload, High Press Hold, Hi Press
Unload, Low Pr Diff/Ration, Hi Motor Amps Hold, Hi Motor Amps
Unload, Hi VFD Amps Hold, Hi VFD Amps Unld, Hi VFD Temp Hold, Hi
VFD Temp Unld, Comp Start Fail, Part Load Shutdown
Current, 2nd Day, 3rd Day, 4th Day, 5th Day, 6th Day, 7th Day
Table 41: Fan VFD Configuration = 1st Fan VFD
Set Point
Fan Stage Up Deadband 0
Fan Stage Up Deadband 1
Fan Stage Up Deadband 2
Fan Stage Up Deadband 3
Fan Stage Up Deadband 4
Fan Stage Up Deadband 5
Fan Stage Down Deadband 1
Fan Stage Down Deadband 2
Fan Stage Down Deadband 3
Fan Stage Down Deadband 4
Fan Stage Down Deadband 5
49
IOM 1242-2 • PATHFINDER
C
o
onTroller
peraTIon
Default Value Loaded
2.5°C (4.5°F)
2.5°C (4.5°F)
4°C (7.2°F)
5°C (9°F)
4°C (7.2°F)
4°C (7.2°F)
4°C (7.2°F)
3.5°C (6.3°F)
3°C (5.4°F)
2.5°C (4.5°F)
2.5°C (4.5°F)
MODEL AWV CHILLERS
®