3.3
Intelligent Output Terminal Function
Intelligent Output Terminal [AL1, AL2-AL0]
The alarm output terminals are connected as shown below by default, or after initialization.
The contact logic can be inverted by using the parameter setting C16.
The relay contacts normally contact a.
Convention uses "normal' to mean the inverter has power and is in Run or Stop Mode.
The relay contacts switch to the opposite position when it is Trip Mode or when input power is off.
During normal running or power is turned off
AL0
AC250V, 2.5A(Resistor load), 0.2A(Inductive load)
DC30V, 3.0A(Resistor load), 0.7A(Inductive load)
Contact a (Initial setting)
AL1
AL2
Contact
Power
Contact
ON
a
ON
(initial
OFF
Setting)
Contact specification
Maximum
When an alarm occurs
Run
AL0-AL1
AL0-AL2
State
Normal
Open
Trip
Closed
-
Open
17
AL0
AL1
AL2
Closed
Open
Closed
Minimum
AC100V, 10mA
DC5V, 100mA