Hyundai N700E Instruction Manual page 55

Hide thumbs Also See for N700E:
Table of Contents

Advertisement

N700E INSTRUCTION MANUAL
N700E INSTRUCTION MANUAL
N700E INSTRUCTION MANUAL
N700E INSTRUCTION MANUAL
Func-
Name
code
Other Function
Start frequency
b10
Adjustment
b11 Carrier frequency setting
Initialization mode
b12
(parameters or trip
history)
Country code for
b13
initialization
b14 RPM conversion facto
STOP key validity during
b15
terminal operation
Resume on FRS
b16
cancellation mode
b17 Communication number
b18 Ground fault setting
Run-
time
Edit
Sets the starting frequency for the inverter output, range is
X
0.50 to 10.00Hz in units of 0.01Hz
Sets the PWM carrier frequency, range is
O
3kHz to 16.0kHz in units of 0.1kHz.
Select the type of initialization to occur, two option codes:
0.... Trip history clear
1.... Parameter initialization
X
(exceptional data)
b13 : Country code
A53 : Rated Motor Voltage
Select default parameter values for country on initialization,
three options,
option codes:
X
0.... Korean version
1.... European version
2.... US version
Specify a constant to scale the displayed
O
RPM for [d08] monitor, range is
0.01 to 99.99 in units of 0.01
Select whether the STOP key on the
keypad is enabled, two option codes:
X
0.... stop enabled
1.... stop disabled
Select how the inverter resumes operation when the free-
run stop (FRS) is cancelled, two options:
X
0... Restart from 0Hz
1....Restart from frequency detected from real speed
of motor
Sets the communication number for communication,
X
range is 1 to 32.
Select the function and level of ground fault..
0 : Do not detect ground fault.
X
0.1~100.0% : Detect ground fault as the % level of
rated current.
19
Description
Defaults
0.50Hz
5.0kHz
0
0
1.00
0
0
1
0.0

Hide quick links:

Advertisement

Table of Contents
loading