Hyundai N700E Instruction Manual page 59

Hide thumbs Also See for N700E:
Table of Contents

Advertisement

N700E INSTRUCTION MANUAL
N700E INSTRUCTION MANUAL
N700E INSTRUCTION MANUAL
N700E INSTRUCTION MANUAL
Func-
code
Output Terminal state setting
Analog meter
C16
gain adjustment
Analog meter
C17
offset adjustment
Output Terminal related function
Overload advance
C18
notice signal level setting
Acceleration arrival signal
C19
frequency setting
Deceleration arrival signal
C20
frequency setting
C21 PID deviation level setting
Run-
Name
time
Edit
O
O
X
X
X
X
Description
Range is 0 to 250, resolution is 1
Range is -3.0 to 10.0% resolution is 0.1
Sets the overload signal level between 50% and
200% resolution is 0.1%.0.5x(Inverter rated current)
∼2.0x
(Inverter rated current)
Motor
current
Over load
signal output
Sets the frequency arrival setting thres-hold for the
output frequency during acceleration. Setting range is
0.0 to A04, resolution is 0.01Hz
Output
frequency
Frequency
arrival signal
Sets the frequency arrival setting threshold for the
output frequency during deceleration, setting range is
0.00 to 400.0Hz resolution is 0.01Hz
Sets the allowable PID loop error magnitude.
Setting range is 0.0 to 100%, resolution is 0.01%
Target value
PID control
Deviation signal
23
(C18)
(C19)
(C20)
Feedback value
(C21)
Defaults
100.0%
0.0%
100.0%
0.00Hz
0.00Hz
10.0%