Hyundai N700E Instruction Manual page 100

Hide thumbs Also See for N700E:
Table of Contents

Advertisement

N700E INSTRUCTION MANUAL
N700E INSTRUCTION MANUAL
N700E INSTRUCTION MANUAL
N700E INSTRUCTION MANUAL
(3) Common specification for 200V/400V class
Inverter model
Control system
Output frequency range
(Note4)
Frequency accuracy
(Note5)
Frequency resolving
power
Voltage/frequency
characteristic
Overload current rate
Acceleration/
Deceleration
DC Braking
Operator
Freque
Extend
ncy
signal
Operator
Run/
Extend
Stop
signal
Intelligent input
terminal
Frequency monitor
Intelligent output
contact
Other functions
Common specification for all model
Space vector modulation PWM system
0.01∼400Hz
Digital command ±0.01% for Max. frequency, analog frequency ±0.1% (25±10℃)
Digital setting : 0.01HZ, Analog setting : Max. frequency / 1,000
V/f control (constant torque, reduced torque), free V/f control
150%, 60sec
0.01∼3000.0 sec (Director, curve setting)
On starting and decelerating by stop command, inverter operates under operation
setting frequency. Or inverter operates with external input (Breaking power, time,
frequency can be set.)
Setting by up/down key
Input voltage : DC0∼+10V (Input impedance 10K )
Input current : 4∼20mA (Input impedance 250 )
Run / Stop key (Forward / Reverse function mode)
Forward run / stop (1a connect, 1b selection possibility)
FW(Forward), RV(Reverse),
CF1~4(Multi-speed bit 1~4), RS(reset),
AT(Analog input change), USP(USP function)
EXT(external trip), FRS(free-run stop), JG(jogging),
SFT(software lock), STA(start), STP(stop), F/R(forward/reverse)
UP(remote control UP), DOWN(remote control DOWN)
Analog meter (DC0~10V full scale. Max · 1mA)
Output frequency, output current and output voltage
OFF for inverter alarm(normally closed contact
output) (Transition to ON for alarm)/Intelligent
output Terminal
AVR function, curved accel/decel. profile, upper and lower limiters,
16-stage speed profile, fine adjustment of start frequency,
carrier frequency change(0.5 to 16Khz), frequency jump, gain and bias setting,
process jogging, electronic thermal level adjustment, retry function,
trip history monitor, auto tuning, V/f characteristic selection, Speed Search
automatic torque boost, frequency conversion display, USP function
2

Hide quick links:

Advertisement

Table of Contents
loading