A36 DC braking force setting
A37 DC braking time setting
Func-
Name
code
Frequency-related Functions
Frequency upper limit
A38
setting
Frequency lower limit
A39
setting
A40
Jump(center) frequency
A42
setting
A44
A41
Jump(hysteresis)
A43
frequency width
A45
setting
PID Control(Note1 : p 4-13)
A46 PID Function selection
Setting range is 0.0 to 5.0sec in units of0.1set.
0
-
Applied level of DC braking force settable from
X
0 to 100% in units o 0.1%
Sets the duration for DC braking, range is
X
0.0 to 10.0 seconds in units of 0.1sec.
Run-
time
Edit
Sets a limit on output frequency less than the maximum
frequency(A04). Range is 0.00 to 400.0Hz in units of
0.01Hz.
Upper limit
X
Lower limit
Sets a limit on output frequency greater than zero.
X
Range is 0.00 to 400.0Hz in units of 0.01Hz
Up to 3 output frequencies can be defined for the
output to jump past to avoid motor resonances
X
(center frequency) range is 0.00 to 400.0Hz in
units of 0.01Hz..
Defines the distance from the center frequency at
which the jump around occurs.
Range is 0.00 to 10.00Hz in units of 0.01Hz
X
Enables PID function, two option codes:
X
0.... PID control disable
1.... PID control enable
11
Free run
Breaking
(A35)
(A37)
Description
(A38)
(A39)
0
Frequency command
(A40)
(A41)
Setting frequency
DC
Time
50.0%
0.0sec
Defaults
Adjustable
range
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0