SiUS121827E

3. Wiring Error Check Function

Outline
Wiring error check function is designed for the microcomputer to correct wiring errors itself.
If local wiring is unclear in the case of buried piping, for example, just press the wiring error check
switch on the outdoor unit. Even if the connections for Room A and Room B are confused, the
system may run without a hassle.
Note that this check function does not work in the following cases.
 For 3-minute standby period after the power is turned on or after the compressor has stopped.
 When the outdoor temperature is below 5°C (41°F).
 If the indoor unit is in trouble (also in case of all-room transmission failure).
When the piping and wiring are perfect, there is no need to use this function.
Procedure
1. Press the wiring error check switch (SW3) on the service monitor PCB of the outdoor unit, and
2. In about 15 ~ 25 minutes, the check finishes automatically.
3. When the check is over, the service monitor LED indicators start blinking.
 Self-correction complete...The LED indicators 1 - 5 blink one after another.
 Self-correction impossible...The LED indicators blink all at the same time.
 Emergency stop...If any of the LED indicators stays on, follow the diagnostic procedure.
Part 7 Trial Operation and Field Settings
the wiring error check function is activated.
LED
1
2
Blinking one after another
Status
All blinking
Any of the LEDs stay on
 Transmission failure occurs at any of the indoor units.
 The indoor unit heat exchanger thermistor is disconnected.
 An indoor unit is in trouble (if a trouble occurs during the wiring error checking).
Wiring error
check switch
3
4
5
Self-correction completed
Self-correction impossible
Emergency stop
Service monitor PCB
A
1
2
3
4
5
(SW3)
(R22003)

Wiring Error Check Function

Judgment
249