Mismatching Of Indoor Unit And Outdoor Unit - Daikin 4MXL-T Series Service Manual

Multi-split type air conditioners
Table of Contents

Advertisement

SiUS121827E
5.7

Mismatching of Indoor Unit and Outdoor Unit

UA
Error Code
Method of Error
The supply power is detected for its requirements (pair type is different from multi type) by the
Detection
indoor/outdoor transmission signal.
Error Decision
The pair type and multi type are interconnected.
Conditions
Supposed
 Wrong models interconnected
Causes
 Wrong wiring of connecting wires
 Wrong indoor unit PCB or outdoor unit PCB mounted
 Defective indoor unit PCB
 Defective outdoor unit PCB
Troubleshooting
Part 6 Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the combination of the
indoor and outdoor unit.
OK?
YES
Are the
connecting wires
connected properly?
YES
NO
NO
Troubleshooting for RA Indoor Unit
Match the compatible models.
Correct the connection.
Check the part numbers of the
indoor and outdoor unit PCB
with the Parts List.
If not matched, change for the
correct PCB.
(R23001)