2. Wiring Error Check Function

Outline
Wiring error check function is designed for the microcomputer to correct wiring errors itself.
If local wiring is unclear in the case of buried piping, for example, just press the wiring error check
switch on the outdoor unit. Even if the connections for Room A and Room B are confused, the
system may run without a hassle. Note that this check function does not work in the following
cases.
When the piping and wiring are perfect, there is no need to use this function.
Procedure
1. Press the wiring error check switch (SW3) on the service monitor PCB of the outdoor unit, and
2. In about 15 ~ 20 minutes, the check finishes automatically.
3. When the check is over, the service monitor LED indicators start blinking.
Trial Operation and Field Settings
For 3-minute standby period after the power is turned on or after the compressor has stopped.
When the outdoor temperature is below 5°C (41°F).
If the indoor unit is in trouble (also in case of all-room transmission failure).
the wiring error check function is activated.
LED
1
2
Blinking one after another
Status
All blinking
Any of the LEDs stay on.
Self-correction completed...The LED indicators 1 ~ 2 (18 class), or 1 ~ 3 (24 class) blink one
after another.
Self-correction impossible...The LED indicators blink all at the same time.
∗ Transmission failure occurs at any of the indoor units.
∗ The indoor heat exchanger thermistor is disconnected.
∗ An indoor unit is in trouble (if a trouble occurs during the wiring error checking).
Emergency stop...If any of the LED indicators stay on, follow the diagnostic procedure.
3
4
5
Self-correction completed
Self-correction impossible
Emergenay stop
Service monitor PCB
A
1
2
3
4
5
Wiring error
check switch
(SW3)

Wiring Error Check Function

Judgment
(R22003)