Brc082A43, Brc082A41W, Brc082A42W(S) Wireless Remote Controller - Daikin 4MXL-T Series Service Manual

Multi-split type air conditioners
Table of Contents

Advertisement

Service Diagnosis
3.4
BRC082A43, BRC082A41W, BRC082A42W(S) Wireless
Remote Controller
Relations
The following modes can be selected by using INSPECTION/TEST OPERATION button on the
Between Modes
remote controller.
Indoor unit settings can be made.
z Filter cleaning sign time
z Others
Press INSPECTION/TEST
OPERATION button once.
Press INSPECTION/TEST
OPERATION button for more
than 4 seconds.
Press INSPECTION/TEST
OPERATION button once.
Following codes can be checked.
z Error codes
z Indoor model code
Service
Diagnosis
To find the error code, proceed as follows:
158
Press INSPECTION/TEST
OPERATION button for
Field
more than 4 seconds.
setting
mode
Normal
After 60
seconds
Inspection
mode
Press INSPECTION/
TEST OPERATION
button once.
Step
Action
1
Press INSPECTION/TEST OPERATION button to enter the inspection mode. Then the
figure 0 blinks on the UNIT No. display.
Service data can be obtained.
z Error code history
z Temperature data of various sections
Service
mode
Service settings can be made.
z Forced fan ON
z Airflow rate setting
Press INSPECTION/TEST
OPERATION button once.
mode
After 10 seconds without starting test operation
or press INSPECTION/TEST OPERATION button once
or 30 min. after the test operation start
Press ON/OFF button within 10 seconds
Test
to start test operation.
operation
Thermostat is forcibly turned on.
mode
Test operation will stop automatically
after 15~30 minutes.
INSPECTION/TEST
OPERATION button