6. Start-Up Check
Set the desired language in parameter 001.
Set motor parameters according to the motor plate:
Motor power
Motor voltage
Motor frequency
Motor current
Rated motor speed
Set frequency interval and ramp times.
Min. reference
Max. reference
Ramp up time
6
Ramp down time
Relay 1 function
Relay 2 function

6.1.5. Motor Start

VLT 5000
VLT 4000
VLT 6000
VLT 8000
Set motor speed in parameter 003 by VLT 5000.
Set motor speed with the +/- keys on LCP of VLT 6000, VLT 8000 and VLT 4000.
Check if the direction of rotation is as shown in the display. It can be changed by swapping two
phases of the motor cable.
VLT 5000
VLT 4000
VLT 6000
VLT 8000
Select total or reduced Automatic Motor Adaptation (AMA) in parameter 107. For further descrip-
tion of AMA, please see the manual.
Press [START] to start the Automatic Motor Adaptation (AMA).
Press [DISPLAY/STATUS] to leave the Quick Menu.
50
Parameter 102
Parameter 103
Parameter 104
Parameter 105
Parameter 106
Parameter 204
Parameter 205
Parameter 207
Parameter 208
Parameter 323
Parameter 326
Press [START] to start the motor
Press [HAND START] to start the motor
Press [STOP] to stop the motor
Press [OFF/STOP] to stop the motor