MINIPLEX Transponder Product Selection (Continued)
Audio Expansion Signal Module and Options
Model
Description
Expansion Signal Module; three, 1.5 A Class B NACs for
4100-5116
Audio applications; up to five maximum per amplifier;
NAC rating = 1.5 A, 50 W, or 100 speakers maximum
Expansion Signal Module NAC Expander; NAC rating =
4100-1266
1.5 A, 50 W, or 100 speakers max.
Expansion Signal Module Class A Adapter; NAC rating =
4100-1267
1.5 A, 50 W, or 100 speakers maximum
Expansion Signal Module Constant Supervision Adapter;
4100-1268
Converts 3 Class B NACs to Constant Supervision
Class B or Class A NACs; for 25 or 70.7 VRMS audio
General Audio Options
Model
Description
4081-9018 End-of-line resistor harness for 70.7 VRMS NACs; 10 k, 1 W
4100-2320 Audio Bay-to-Bay Interconnection Harness Kit; order one for each audio bay addition
4100-0637 Audio Box Interconnection Harness Kit; order one for each close-nippled audio cabinet
Addressable Interface Modules
Model
Description
IDNet 1+ Module, 250 point capacity with
4100-3108
isolated output, 1 block
Quad IDNet Isolator Module; converts a single connected SLC into four isolated outputs selectable as
Class A or Class B, provides advanced diagnostics for use with retrofit wiring; dual horizontal block
4100-3107
module; (see data sheet S4100-0046 for additional details)
NOTE: This module is compatible with IDNet Remote Isolators
Relay Modules; Nonpower-Limited
Model
Description
4100-3202 4 DPDT w/feedback
4100-3204 4 DPDT w/feedback
4100-3206 8 SPDT
Current Calculation Notes:
1.
For total supervisory current, add panel module currents to base system value and add all external panel-powered loads.
2.
For total alarm current, add panel module currents to base system alarm current and add all panel SLC/NAC loads and all external
loads powered from panel power supplies.

General Specifications

Enhanced Power Supplies,
Input Power
Expansion Power Supply (XPS)
Power Supply Output
IDNAC Output Voltage Regulated 29 VRMS
Ratings for EPS/EPS+
Power Supply Output
Ratings for XPS
(nominal 28 VDC on AC;
24 VDC on battery
backup)
Compatible Special Application Appliances
Battery Charger
Battery capacity range
Ratings for EPS/EPS+
(sealed lead-acid
Charger characteristics
batteries)
Operating Temp. Range 32° to 120°F (0° to 49° C)
Environmental
Operating Humidity Range Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Installation Instruction Reference
Resistive Ratings
10 A
250 VAC
2 A
30 VDC/VAC
3 A
30 VDC/120 VAC
120 VAC Models
EPS/EPS+
220-240 VAC Models
120 VAC Models
100 W Amplifiers
220-240 VAC Models
Total Power Supply
Including module currents and auxiliary power outputs; 9 A
Output Rating
total for "Special Application" appliances
Auxiliary Power Tap 2 A maximum
9 A total including module currents and auxiliary power
Total Power Supply
Output Rating
outputs
Auxiliary Power Tap 2 A maximum
NACs Programmed
2 A maximum per NAC;
for Auxiliary Power
5 A maximum total
Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact your
Simplex product representative for compatible appliances
UL listed for battery charging of 6.2 Ah up to 115 Ah (batteries larger than 50 Ah
require a remote battery cabinet); ULC listed for charging up to 50 Ah batteries
Temperature compensated, dual rate, recharges depleted batteries within 48 hours per
and performance
UL Standard 864, to 70% capacity in 12 hours per ULC Standard S527
574-844, Transponder Interface Cards
Details and Mounting Reference
Converts one NAC input to three NAC outputs; selects between two
inputs; for Flex-35/50 amplifiers only, two input NACs are required;
Single Block module mounts in expansion bay;
Supv = 20 mA; Alarm = 80 mA
Expands module capacity to six, Class B NACs;
Supv = 0.84 mA; Alarm = 60 mA
Converts 3 Class B, NACs to Class A;
Supv = 0 mA; Alarm = 30 mA
NAC rating = 1.4 A, 50 W, or 100 speakers max.;
Supv = 38 mA on batteries (constant supervision
deactivated); Alarm = 70 mA
With 250 IDNet devices, and 20 device LEDs in alarm 292 mA
Loading per IDNet device (no LEDs on)
Inductive Ratings
10 A
250 VAC
½ A
30 VDC/120 VAC
1 ½ A
30 VDC/120 VAC
4.6 A maximum @ 102 to 132 VAC, 50/60 Hz
2.3 A maximum @ 204 to 264 VAC, 50/60 Hz;
separate taps for 220/230/240 VAC
4 A maximum @ 102 to 132 VAC, 60 Hz
2 A maximum @ 204 to 264 VAC, 50/60 Hz;
separate taps for 220/230/240 VAC
Rated 19.1 to 31.1 VDC
6
These modules
mount on the
4100-5116;
select one
max. per
4100-5116 as
required
Supv.
Module without devices
92 mA
0.8 mA
75 mA
Size
Supv.
2 Slots
15 mA
1 Block
15 mA
1 Block
15 mA
Output switches to
battery backup
during mains AC
failure or brownout
conditions
579-343, Local Mode Controller
S4100-0103 5/2013
Alarm
510 mA
115 mA
1 mA
115 mA
Alarm
175 mA
60 mA
190 mA

Advertisement